Plan Review Notes
Plan Review Notes For Permit 19100015
Permit Number 19100015
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-23 10:54:41RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- PLANS SUBMITTED ARE MISSING SHEET S-5 LISTED ON THE
 SHEET INDEX ON SHEET D1. PROVIDE COMPLETE SET OF
 DRAWINGS, INCLUDING SHEET S-5. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 4- PROPOSED FLOOR PLAN ON SHEET S1 AND FOUNDATION PLAN
 ON SHEET S4 DON'T MATCH. FOUNDATION PLAN SHOWS DOORS
 LEADING TO THE NEW PATIO AREA BUT FLOOR PLAN DON'T SHOW
 ANY DOORS. (ELECTRICAL PLAN SHOWS DOORS ALSO).
 CLARIFY/REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS..
  
 5- THERE IS ONE WINDOW ON EXISTING BEDROOM #3 THAT IS
 GOING TO BE BLOCKED TO ALLOW FOR THE ADDITION. SPECIFY
 SIZE OF EXISTING WINDOW TO REMAIN ON THE SAME BEDROOM
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC.
 1101.1 FBC-EXISTING BUILDING AND SEC. R310.2
 FBC-RESIDENTIAL.
  
 6- REVISE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS
 SHOWN ON SHEET S1. DETAILS SHOW TAPERED BUCKS. TAPERED
 BUCKS ARE NOT ALLOWED ANYMORE AND THE BUCK NEEDS TO
 EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME (PROVIDE FULL SUPPORT TO THE WINDOW/DOOR FRAME).
 SEC. R609.7.2 FBC-RESIDENTIAL.
  
 7- REVISE "DESIGN DATA FOR WIND LOADS" ON SHEET S2:
 THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT EXPOSURE
 "B". REVISE AS REQUIRED AND REVISE DESIGN PRESSURES
 ACCORDINGLY. AND, CLEARLY SPECIFY IF THE DESIGN
 PRESSURES SHOWN ON THE SCHEDULE ARE ULTIMATE DESIGN
 PRESSURES OR NOMINAL DESIGN PRESSURES. SEC. R301.2.1.4
 FBC-RESIDENTIAL.
  
 8- ROOF FRAMING PLAN SHOWN ON SHEET S3:
 A) IT IS MISSING THE BEAM BETWEEN THE TWO NEW BEDROOMS
 AT THE NEW PATIO AREA. PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR THIS BEAM. SEC. 1101.1 FBC-EXISTING
 BUILDING AND SEC. R301.1 FBC-RESIDENTIAL.
  
 B) ROOF FRAMING PLAN DOESN'T MATCH ROOF PROFILE SHOWN
 ON THE EXTERIOR ELEVATIONS ON SHEET S2. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 9-SHEET S2:
 A) SCREEN ENCLOSURE DETAILS/SPECS SHOWN DON'T MATCH
 PLANS. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 SITE SPECIFIC INSTALLATION OF THE SCREEN ENCLOSURE THAT
 MATCHES PROPOSED INSTALLATION IN THIS ADDITION. SPECIFY
 ALL FRAMING MEMBERS AND CONNECTIONS. SEC.
 R301.2.1.1.1.1 FBC-RESIDENTIAL OR SEC. R301.2.1.1.2
 FBC-RESIDENTIAL
  
 B) WINDOW SIZE SHOWN ON ALL THE EXTERIOR ELEVATIONS
 DON'T MATCH SIZE SPECIFIED ON ON THE WINDOW SCHEDULE ON
 SHEET S1. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) WINDOWS AS SHOWN ON PLANS.
  
 C) SHUTTERS IF DOORS/WINDOWS DON'T HAVE IMPACT GLAZING.
 AND PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) ROOF SHINGLES AS SPECIFIED ON PLANS.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S (APPLIES TO OWNER/BUILDER TOO) OVERHEAD
 AND PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO
 $77,810. THE PERMIT FEE BALANCE IS $1855.78.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,