| 2019-10-07 05:17:58 | 1) THE LETTER FOR THE ALTERNATE APPROVAL FOR THE DRAIN |
| | TO A DRYWELL IS FOR SHOWER EFFLUENT BUT THE SUBMITTED |
| | "DETAIL E" NOTES THE DRAIN FROM A DRINKING FOUNTAIN. |
| | WHICH IS IT? CLARIFY. A REVISED LETTER WILL BE REQUIRED |
| | OR A REVISED DETAIL IF IT FOR A SHOWER. |
| | 2) THE LETTER FOR THE ALTERNATE APPROVAL OF THE DRAIN |
| | TO THE DRYWELL AND THE CORRESPONDING DETAIL SHALL BEAR |
| | THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL PER |
| | FL. ADMIN. CODE RULE 61G15-23.001. |
| | 3) TWO DIFFERENT SPECIFICATIONS HAVE BEEN SUBMITTED FOR |
| | THE DRINKING FOUNTAINS ( 1035 SMSS & 10155 SM). WHICH |
| | UNIT IS BEING INSTALLED. CLARIFY. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 4) SHT.L3.11 - DETAIL "C" - THE MAXIMUM HEIGHT TO THE |
| | BOTTLE FILLER CONTROLS AND BOTTLE SHELF SHALL BE 48 |
| | INCHES PER THE 2017 FBC-ACCESSIBILITY SECS.308.2, |
| | 308.3, 309. |
| | 5) SHT.L3.11 - DETAIL "C"- THE MAXIMUM HEIGHT OF THE |
| | WATER SPOUT SHALL BE 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND PER 2017 FBC-ACCES. SEC. 602.4 FOR |
| | ACCESSIBLE FOUNTAINS FOR USE BY PEOPLE IN WHEELCHAIRS. |
| | MODEL 10155 SM DOES NOT COMPLY AS SHOWN ON THIS DETAIL. |
| | 6) THE DETAIL FOR DRINKING FOUNTAIN 10155 SM SHOWN ON |
| | SHT. L3.11 DOES NOT CORRELATE WITH THE MANUFACTURER'S |
| | SPECIFICATION SHEET THAT HAS BEEN SUBMITTED FOR THIS |
| | SAME MODEL IN REGARDS TO THE HEIGHT OF THE DRINKING |
| | FOUNTAIN ABOVE THE FINISH FLOOR OR GROUND. CLARIFY. |
| | 7) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| | PERSONS SHALL BE 38 INCHES MINIMUM AND 43 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER 2017 FBC- |
| | ACCESS. SEC. 602.7. |
| | 8 ) THE HEIGHT OF THE SPOUT FOR PEOPLE IN WHEELCHAIRS |
| | SHALL BE LOCATED A MAXIMUM OF 36 INCHES ABOVE THE |
| | FINISH FLOOR OR GROUND. REFER TO THE MANUFACTURER'S |
| | SPECIFICATION SHEET FOR MODEL 10135 SMSS. |
| | 9) WHO IS THE MANUFACTURER FOR DRINKING FOUNTAIN MODEL |
| | 10135 SMSS? THE IS NO MANUFACTURER LISTED ON THE |
| | SPECIFICATION SHEET. CLARIFY.SUBMIT SPEC SHEET THAT |
| | SHOWS THE MANUFACTURER.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) ALL PLUMBING PRODUCTS AND MATERIALS SHALL BE LISTED |
| | BY A THIRD- PARTY CERTIFICATION AGENCY AS COMPLYING |
| | WITH THE REFERENCED STANDARDS. THE SUBMITTED |
| | SPECIFICATION SHEETS FOR THE DRINKING FOUNTAINS OR THE |
| | SHOWER DO NOT SHOW ANY TYPE OF LISTING OR |
| | CERTIFICATION.SUBMIT SPECIFICATION SHEETS THAT COMPLY. |
| | 11) THE SUBMITTED SPECIFICATION SHEETS FOR THE SHOWER |
| | SHOW THE HEIGHT OF THE SHOWER CONTROLS IN SI UNITS OF |
| | MEASUREMENT ( MILLIMETERS? ). SHOW THE HEIGHT OF THE |
| | SHOWER CONTROL IN U.S. CUSTOMARY SYSTEM UNITS OF |
| | MEASUREMENT. WPB AMEND. TO FBC SEC. 107.2.1.THE HEIGHT |
| | OF THE CONTROL SHALL COMPLY WITH THE 2017 FBC- ACCESS. |
| | SECS. 308 & 309. |
| | 12) RESPONSE #2 OF THE RESPONSE NARRATIVE REFERS TO |
| | CORRESPONDENCE FROM THE MANUFACTURER OF THE DRINKING |
| | FOUNTAINS INDICATING COMPLIANCE WITH THE FLORIDA |
| | ACCESSIBILITY CODE. THERE IS NO SUCH CORRESPONDENCE IN |
| | THE SUBMITTAL PACKAGE. CLARIFY. |
| | |