Plan Review Notes
Plan Review Notes For Permit 19091166
Permit Number 19091166
Review Stop M
Sequence Number 2
Notes
Date Text
2020-08-26 13:54:273RD REVIEW FBC-2017 MECHANICAL
 PERMIT-19091166
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-202: WHY DID THE CONDENSATE LINE REDUCE FROM
 1 ?? TO ??? FBC FS 107.2.1
  
 2) PLEASE PROVIDE DETAILS OF WHERE THE CONDENSATE IS
 BEING DRAINED TO AT THE EXTERIOR OF THE BUILDING. FBC
 FS 107.2.1
  
 3) NOTE 3 OF 2ND CYCLE REVIEW MENTIONED ?THE APPLIANCES
 DO NOT INDICATE THAT THEY HAVE BEEN TESTED IN
 ACCORDANCE WITH ANSI Z21.1, Z21.58 OR Z83.11?. ANSI
 Z21.1 AND Z21.58 DO NOT APPLY AS THEY ARE FOR
 RESIDENTIAL APPLIANCES. PLEASE NOTE THAT ANSI Z83.11-
 2013 EDITION DOES APPLY. THE COFC SUBMITTED REFERENCES
 ANSI Z 83.11-2006. AS WE ARE IN THE 2017 FLORIDA
 BUILDING CODE MECHANICAL AND IT REFERENCES ANSI
 Z83.11-2013 THE SUBMITTED DOCUMENT MUST BE CHANGED. THE
 COFC LETTER IS DATED 2008/10/20 BUT THE ANSI Z83.11-
 2006 VERSION. PLEASE PROVIDE A COFC WITH A DATE
 COINCIDING WITH THE 2013 EDITION OF ANSI Z83.11.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-02-25 12:36:392ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19091166
 2/25/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100: CORRECT THE PROJECT CODE COMPLIANCE DATA
 TO INDICATE THE CURRENT 2017 6TH EDITIONS OF THE
 FLORIDA BUILDING CODES.
  
 2) M103: ACCORDING TO NOTE #4 UNDER THE VENTILATION
 SCHEDULE THE O/A IS PROVIDING THE REQUIRED 530 CFMS OF
 COMBUSTION AIR, HOWEVER THE SCHEDULE INDICATES 389.6
 CFMS FOR THE KITCHEN. PLEASE REFER TO SECTION 304.9.3
 FBC FG: WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. IN ADDITION,
 PLEASE NOTE THAT THERE ARE NO SUPPLY DIIFFUSERS LOCATED
 AT THE COOKING LINE.
  
 3) M103: CORRECT THE SPLIT SYSTEM AC SCHEDULE WHICH IS
 INDICATING ALL 4 SYSTEMS SERVING THE DINING AREA. AHU 3
 & 4 ARE SUPPLYING THE PREP AND KITCHEN AREAS- SECTION
 107.2.1 WPB.
  
 4) M103: THE 14,500 CFMS FOR THE PRF-1 IN THE AIR
 BALANCE SCHEDULE DOESN'T MATCH THE 12,500 CFMS LISTED
 FOR THE FAN IN NTHE FAN SCHEDULE. PLEASE NOTE THE FAN
 IS MISLABELED REF-1 IN THE FAN SCHEDULE- SECTION
 107.2.1 WPB.
  
 5) M200: CORRECT NOTE #11 SPECIFYING CONDENSATE TO
 DRAIN INTO THE SANITARY SYSTEM WHICH IS PROHIBITED PER
 SECTION 90-126 WPB CODE OF ORDINANCES.
  
 6) 2ND REQUEST FOR ENGINEERING FOR INSTALLATION OF THE
 ROOFTOP MECHANICAL EQUIPMENT AND THE LOUVERED
 PENTHOUSE- SECTION 301.15 FBC M. PLEASE NOTE THE
 ENGINEERING MAY BE A DEFERRED SUBMITTAL IF REQUESTED-
 SEE SECTION107.3.4.1 WPB.
  
 7) THE SUBMITTALS FOR THE JADE GAS-FIRED COOKING
 APPLIANCES DO NOT INDICATE THE UNITS HAVE BEEN TESTED
 IN ACCORDANCE WITH ANSI Z21.1, Z21.58, OR Z83.11- SEE
 SECTION 623.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER