| 2020-08-26 13:54:27 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT-19091166 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-202: WHY DID THE CONDENSATE LINE REDUCE FROM |
| | 1 ?? TO ??? FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE DETAILS OF WHERE THE CONDENSATE IS |
| | BEING DRAINED TO AT THE EXTERIOR OF THE BUILDING. FBC |
| | FS 107.2.1 |
| | |
| | 3) NOTE 3 OF 2ND CYCLE REVIEW MENTIONED ?THE APPLIANCES |
| | DO NOT INDICATE THAT THEY HAVE BEEN TESTED IN |
| | ACCORDANCE WITH ANSI Z21.1, Z21.58 OR Z83.11?. ANSI |
| | Z21.1 AND Z21.58 DO NOT APPLY AS THEY ARE FOR |
| | RESIDENTIAL APPLIANCES. PLEASE NOTE THAT ANSI Z83.11- |
| | 2013 EDITION DOES APPLY. THE COFC SUBMITTED REFERENCES |
| | ANSI Z 83.11-2006. AS WE ARE IN THE 2017 FLORIDA |
| | BUILDING CODE MECHANICAL AND IT REFERENCES ANSI |
| | Z83.11-2013 THE SUBMITTED DOCUMENT MUST BE CHANGED. THE |
| | COFC LETTER IS DATED 2008/10/20 BUT THE ANSI Z83.11- |
| | 2006 VERSION. PLEASE PROVIDE A COFC WITH A DATE |
| | COINCIDING WITH THE 2013 EDITION OF ANSI Z83.11. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |
| 2020-02-25 12:36:39 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19091166 |
| | 2/25/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M100: CORRECT THE PROJECT CODE COMPLIANCE DATA |
| | TO INDICATE THE CURRENT 2017 6TH EDITIONS OF THE |
| | FLORIDA BUILDING CODES. |
| | |
| | 2) M103: ACCORDING TO NOTE #4 UNDER THE VENTILATION |
| | SCHEDULE THE O/A IS PROVIDING THE REQUIRED 530 CFMS OF |
| | COMBUSTION AIR, HOWEVER THE SCHEDULE INDICATES 389.6 |
| | CFMS FOR THE KITCHEN. PLEASE REFER TO SECTION 304.9.3 |
| | FBC FG: WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR. IN ADDITION, |
| | PLEASE NOTE THAT THERE ARE NO SUPPLY DIIFFUSERS LOCATED |
| | AT THE COOKING LINE. |
| | |
| | 3) M103: CORRECT THE SPLIT SYSTEM AC SCHEDULE WHICH IS |
| | INDICATING ALL 4 SYSTEMS SERVING THE DINING AREA. AHU 3 |
| | & 4 ARE SUPPLYING THE PREP AND KITCHEN AREAS- SECTION |
| | 107.2.1 WPB. |
| | |
| | 4) M103: THE 14,500 CFMS FOR THE PRF-1 IN THE AIR |
| | BALANCE SCHEDULE DOESN'T MATCH THE 12,500 CFMS LISTED |
| | FOR THE FAN IN NTHE FAN SCHEDULE. PLEASE NOTE THE FAN |
| | IS MISLABELED REF-1 IN THE FAN SCHEDULE- SECTION |
| | 107.2.1 WPB. |
| | |
| | 5) M200: CORRECT NOTE #11 SPECIFYING CONDENSATE TO |
| | DRAIN INTO THE SANITARY SYSTEM WHICH IS PROHIBITED PER |
| | SECTION 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 6) 2ND REQUEST FOR ENGINEERING FOR INSTALLATION OF THE |
| | ROOFTOP MECHANICAL EQUIPMENT AND THE LOUVERED |
| | PENTHOUSE- SECTION 301.15 FBC M. PLEASE NOTE THE |
| | ENGINEERING MAY BE A DEFERRED SUBMITTAL IF REQUESTED- |
| | SEE SECTION107.3.4.1 WPB. |
| | |
| | 7) THE SUBMITTALS FOR THE JADE GAS-FIRED COOKING |
| | APPLIANCES DO NOT INDICATE THE UNITS HAVE BEEN TESTED |
| | IN ACCORDANCE WITH ANSI Z21.1, Z21.58, OR Z83.11- SEE |
| | SECTION 623.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |