Plan Review Notes
Plan Review Notes For Permit 19091166
Permit Number 19091166
Review Stop B
Sequence Number 2
Notes
Date Text
2020-02-11 15:36:56RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE NOTE ON THE DRAWINGS THAT TERMITE PROTECTION
 IS REQUIRED FOR THE REPLACEMENT SLAB PER FBC 1816
 2) PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE ROOF
 TOP SHAFT TERMINATION - SHOW ALL MATERIALS AND
 ATTACHMENTS.(FRAMING, PLYWOOD ATTACHMENTS ETC.) FBC
 1609.1
 3) PLEASE PROVIDE A ROOFING PERMIT APPLICATION FOR THE
 ROOF TOP SHAFT TERMINATION ROOF. ( IF NOT PROVIDED -
 THE ROOFING WILL BE A PROVISO ITEM (DEFFERRED)).
 4) PLEASE PROVIDE ROOFING PRODUCT APPROVALS. FBC 1503
 5) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND
 INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS THAT ARE
 LISTED ON THE DRAWINGS FOR THE WINDOWS AND DOORS.
 (PRODUCT APPROVALS PROVIDED ARE NOT LISTED ON THE
 DRAWINGS AND ARE NOT COMPLETE). FBC 1609.1.2
 6) DOOR MARKED (101) CANNOT BE AN INSWING DOOR - FBC
 1010.1 " DOORS PROVIDED FOR EGRESS PURPOSES IN NUMBERS
 GREATER THAN REQUIRED BY THIS CODE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION".
 7) DOOR MARKED (108A)" WOMANS TOILET ROOM"NEEDS TO MEET
 ADA REQUIREMENTS. DOOR SCHEDULE SHOWS A 2 FOOT WIDE
 DOOR. FBC ACCESSIBILITY 404.2.3
 8) ROOF TOP AC ATTACHMENTS - SHOW ALL ATTACHMENT SIZES,
 TYPES, LENGTHS ETC. FBC WPB AMENDMENTS 107
 9) WIND DESIGN PRESSURES SHOWN ON DRAWING S1.0 - APPEAR
 TO BE VERY HIGH - PLEASE RE EVALUATE - ROOF HEIGHT 58'?
 - PRODUCT APPROVALS ARE REQUIRED TO MEET THE DESIGN
 PRESSURES SHOWN.
 10) ANY DEFERRED SUBMITTALS WILL NEED TO BE IN WRITING.
 (PRODUCT APPROVALS, ROOFING SYSTEM ETC.)