| Plan Review Notes For Permit 19091166 |
| Permit Number |
19091166 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-25 11:47:10 | FAILED | | | | | | 1) THERE IS NEW MECHANICAL EQUIPMENT BEING INSTALLED ON | | | THE ROOFTOP. PROVIDE A SITE LINE OR OTHER DRAWING TO | | | VERIFY THAT THE FULL HEIGHT OF THE NEW EQUIPMENT, | | | INCLUDING THE CURB, IS SCREENED IN ACCORDANCE WITH THE | | | REQUIREMENTS OF THE CITYPLACE DRI. THE MAU APPEARS TO | | | BE APPROXIMATELY EIGHT (8) FEET ABOVE THE ROOF. | | | | | | 2) THE ELEVATION DRAWINGS ARE MISLABELED AS TO WHICH | | | ELEVATION EACH ONE IS. | | | | | | 3) PROVIDE THE TRANSPARENCY CALCULATIONS FOR EACH | | | ELEVATION. A MINIMUM OF 50% IS REQUIRED. VERIFY THAT | | | GLASS TYPE GL-5 IS TRANSPARENT. | | | | | | 4) PLEASE NOTE: SOME OF THE SIGNAGE LOCATIONS MAY NOT | | | CONFORM TO MASTER SIGN PLAN. SIGN LOCATIONS WILL BE | | | REVIEWED AT TIME OF SIGN PERMIT AND ARE NOT APPROVED AS | | | PART OF THIS PERMIT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | |
|