2019-10-28 09:20:26PLUMBING 1ST REVIEW**DENIED**19091166
  
 1) SHT ADA1.1 DETAIL #4 PLEASE SHOW 40? MAX IS TO THE
 REFLECTIVE SURFACE AND NOT THE BOTTOM OF THE MIRROR.
 FBC-ACC 603.3
 2) SHT ADA1.1 DETAIL #3 SHOW THE 7?-9? TO THE FIRST
 ROLL AND NOT TO THE CENTER OF MUILT ROLL DISPENSER.
 REFER TO FBC-ACC 604.7
 3) ALL NOTE ALL HOT WATER AND RETURN HOT WATER SHALL BE
 INSULATED WITH MIN 1? WALL AND FOLLOW SIZING PER
 FBC-ENERGY C404.4.
 4) SHT. P106 L-2 IN MEN?S AND WOMEN?S TOILET ROOM NOT
 SHOWN ON WATER RISER. FBC 107.3.5
 5) SHT. P106 EMPLOYEE TOILET ROOM FIXTURES L-3 & W-3ARE
 LABELED AS L-2 & L-3 ON WATER ISO. PLEASE CLARIFY. FBC
 107.2.1
 6) P-165 IS SHOWN ON THE RISER BUT NOT ON THE FLOOR
 PLAN SHT.201
 7) P-406 SHOWN ON FLOOR PLAN ON SHT. P201 BUT NOT ON
 WATER ISO. PLEASE CLARIFY FBC 107.2.1
 8) SHT.P107 CLEAN-OUTS ARE REQUIRED IN WASTE STACKS,
 MOP SINKS, FLOOR DRAINS IN THE KITCHEN AREA AND SHALL
 DISCHARGE INTO THE GREASE SYSTEM. FBC-107.3.5
 9) P-107 IS THIS SUPPOSE TO BE AN ISLAND VENT? PLEASE
 CLARIFY 107.2.1
 10) P-107 LAVATORIES L-2 IN MEN?S AND WOMEN?S TOILETS
 ROOMS ARE LABELED AS L-1 ON SANITARY RISER. PLEASE
 CLARIFY. FBC 107.2.1
 11) P-107 LAVATORY L-3 IN EMPLOYEE TOILET ROOM IS
 LABELED AS L-1 ON SANITARY RISER. PLEASE CLARIFY. FBC
 107.2.1
 12) SHT. EM 1.1 OCCUPANT LOAD IS LISTED AS 261 BUT
 FIXTURES LOAD IS LISTED AS 278. PLEASE CLARIFY FBC
 107.2.1.
 13) SHT. SP1.1 KEYNOTE #9 CALLS OUT EXISTING WALL
 HYDRANT TO REMAIN BUT THIS LINE IS A SPRINKLER LINE.
 PLEASE CLARIFY. FBC 107.2.1
 14) FOOD SERVICE DRAWINGS SHALL BE SIGNED AND SEALED.
 F.S 471,481
 15) 3- COMPARTMENT AND 2-COMPARTMENT SINKS SHALL BE
 PIPED INDEPENDENTLY TO THE FLOOR SINK. FBC-PLB 802.1.1
 16) PLEASE ADD NOTE BACKFLOW DEVICE REQUIRED ON ALL
 REQUIRED EQUIPMENT.
 17) SHT. P100 CALLS OUT HOT WATER DEMAND PIPING TO
 PUBLIC LAVS TO BE 140F. ALL HAND WASH SINKS SHALL BE
 TEMPERED BY AN APPROVED ASSE 1070 DEVICE TO A MAX TEMP
 OF 110F. FBC-PLB 607.1.2
 18) SHT. P107 SANITARY ISOMETRIC PLEASE SIZE ALL PIPING
 INCLUDING VENTS. FBC 107.3.5
 19) SHT.P104 DETAIL #8 TEMPERING VALVES SHALL BE AN
 APPROVED ASSE 1070 VALVE.
 20) SHT. P104 BACKFLOW SCHEDULE. PLEASE NOTE ALL
 BACKFLOWS ARE REQUIRED TO BE LEAD FREE. THE 975 XL
 CALLED OUT IS NOT LEAD FREE. NSF 61 AND WPB CROSS
 CONNECTION MANUAL 2017.
 21) NOTE ON PLAN ALL NEW MAIN BACKFLOW AND GREASE
 INTERCEPTOR REQUIRED SEPARATE PERMITS. FBC 105.1
 22) SHT. 101 UNDER INSPECTIONS TEST REQUIREMENTS YOU
 CALL OUT AIR. AIR TEST IS NOT PERMITTED ON PLASTIC
 PIPING. FBC 312
 23) SHT.101 TOTAL SINK AND EQUIPMENT GPM CAPACITY I
 COME UP WITH 172. PLEASE CLARIFY 107.2.1
 TIM HUNT
 PLUMBING PLAN EXAMINER
 CITY OF WEST PALM BEACH ( CGA SOLUTIONS)