| 2019-11-05 15:21:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19091166 |
| | 11/5/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION C403.2.1 FBC-EC. |
| | |
| | 2) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER |
| | HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC-17 |
| | ENERGY CONSERVATION. SUBMIT A COMMISSIONING PLAN AS |
| | OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS |
| | C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY OF THE |
| | COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT |
| | FINAL INSPECTION. |
| | |
| | 3) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| | EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALKIN |
| | COOLER- SECTION 107.2.1 WPB. PLEASE PLACE A BOLD NOTE |
| | ON THE PLAN FOR CLARIFICATION. |
| | |
| | 4) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE |
| | NEW GAS COOKING APPLIANCES AND PROVIDE CALCULATIONS- |
| | SECTION 304 FBC FG. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GAS-FIRED COOKING APPLIANCES- |
| | SECTION 623.1 FBC FG. PLEASE NOTE THE SPECS MAY BE |
| | DEFERRED SUBMITTALS IN ACCORDANCE WITH |
| | SECTION107.3.4.1WPB. |
| | |
| | 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW AIR |
| | HANDLERS. SHOW THE TYPE AND SIZE OF CONDENSATE PIPINGS, |
| | THE PIPING RUNS, AND DISCHARGE LOCATION- SECTION 307.2 |
| | FBC M. PLEASE NOTE THAT CONDENSATE FROM COOLING COILS |
| | SHALL NOT DRAIN INTO THE CITY SANITARY SYSTEM- SECTION |
| | 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 6) PROVIDE ENGINEERING FOR INSTALLATION OF THE ROOFTOP |
| | MECHANICAL EQUIPMENT AND THE LOUVERED PENTHOUSE- |
| | SECTION 301.15 FBC M. |
| | |
| | 7) CLARIFY IF THE NEW AC SYSTEMS ARE INCLUDED IN THE |
| | $950,000 JOB VALUE. REFER TO THE NOTE ON SHEET M400 |
| | THAT STATES THE AC SYSTEMS ARE LANDLORD SUPPLIED AND |
| | CLARIFY IF THE NEW COST OF THE SYSTEMS ARE INCLUDED IN |
| | THE $950,000 JOB VALUE- SEE SECTION 109.3 WPB AND |
| | SUBMIT COPIES OF CONTRACTS, INVOICES, ETIMATES ETC. |
| | |
| | 8) THE MECHANICAL ENGINEER OF RECORD JOHN M.THOMAS MAY |
| | NOT SELF-CERTIFY HIS SEAL AND SIGNATURE. THE SEAL AND |
| | SIGNATURE MUST HAVE THIRD-PARTY VERIIFCATION. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |