2019-10-04 14:30:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET EM 1.1 - THERE IS AN INDICATION OF AN EXIT
 DOOR, #101, SWINGING AGAINST THE PATH OF TRAVEL.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 1.1 - IN THE TRAVEL PATH TO THE REAR EXIT,
 THERE APPEARS TO BE EQUIPMENT LOCATED ALONG THE WAY
 THAT CAN BE DISLODGED AND/OR IS AN OBSTRUCTION.
  
 ADDITIONALLY, THE LOCATED EQUIPMENT MAY EXTEND INTO THE
 REQUIRED EXIT WIDTH; HOWEVER, NO DIMENSIONS ARE
 PROVIDED.
  
 PER NFPA 101 CH 7 MEANS OF EGRESS
  
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
 7.1.10.2 FURNISHINGS AND DECORATIONS IN MEANS OF
 EGRESS.
 7.1.10.2.1 NO FURNISHINGS, DECORATIONS, OR OTHER
 OBJECTS SHALL
 OBSTRUCT EXITS OR THEIR ACCESS THERETO, EGRESS THERE
 FROM, OR
 VISIBILITY THEREOF.
  
 7.3.4 MINIMUM WIDTH.
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE
 PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3, SHALL BE AS
 FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN
 THIS CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS
 CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY A
 MINIMUM WIDTH
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET A 9.1 - DOOR 100 & 101 INDICATES A DOOR LATCH
 TYPE HARDWARE SET WITH CYLINDER AND DEAD BOLTS .
  
 PER NFPA 101 CH 12, NEW ASSEMBLIES AND CH 7 MEANS OF
 EGRESS
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
  
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET
 ALL OF THE
 FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF THE
 WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED
 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND
 LATCHES.
  
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER
 THAN DETENTION AND CORRECTIONAL OCCUPANCIES AS
 OTHERWISE PROVIDED
 IN CHAPTERS 22 AND 23, SHALL NOT BE EQUIPPED WITH ANY
 LOCKING
 DEVICE, SET SCREW, OR OTHER ARRANGEMENT THAT PREVENTS
 THE RELEASE
 OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING
 DEVICE.
 7.2.1.7.4 DEVICES THAT HOLD THE LATCH IN THE RETRACTED
 POSITION SHALL
 BE PROHIBITED ON FIRE EXIT HARDWARE, UNLESS SUCH
 DEVICES ARE LISTED
 AND APPROVED FOR SUCH A PURPOSE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 AND NARRATIVE.
  
  
  
 4) FS 8.0 - UNDER FIRE PROTECTION SYSTEM NOTES THE IS
 AN INDICATION OF A FIRE SUPPRESSION SYSTEM.
  
 THE FIRE SUPPRESSION SYSTEM SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) SHEETS M 104 & 105 - THERE ARE INDICATIONS OF A HOOD
 SYSYEM OVER THE KITCHEN EQUIPMENT.
  
 THE HOOD SYSTEM SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 6) SHEETS SP 1.1 & 1.2 - THERE IS AN INDICATION OF A
 PATIO I DINING AREA THAT EXTENDS OUT INTO THE OPEN
 AREA; HOWEVER, THERE ARE NO DIMENSIONS OR LOCATIONS OF
 NEAREST OTHER STRUCTURES.
  
 THE CONCERN HERE IS THAT THIS EXTENSION DOES NOT REDUCE
 FREE EGRESS FROM OTHER AREAS OF THE PLAZA.
  
 PLEASE PROVIDE ALL APPLICABLE STRUCTURES WITH
 DIMENSIONS.
  
  
  
 7) SHEETS SP 1.1 & 1.2 - THERE IS AN INDICATIONS OF A
 PATIO I & PATIO II DINING AREAS THAT EXTENDS OUT INTO
 THE OPEN AREAS.
  
 WILL THERE BE ANY PROPOSED ROOF OR CANOPY STRUCTURES
 OVER THESE AREAS.
  
 PLEASE REVIEW AND PROVIDE COMMNETS AND/OR DETAILS.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL