Notes
Date Text
2019-10-07 11:56:10FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E101
  
 1) FAULT CURRENT CALCULATION TO BE ADDRESSED ON PLANS.
  
 2) NO LOAD CALCULATION SHOWN JUST A DEMAND AND AN
 ADJUSTED LOAD?
  
 PAGE E300
  
 1) STORAGE ROOM SHOWS A DISONNECT WITHOUT WORKING
 CLEARANCE?
  
 2) 225 KVE TRANSFORMER ABOVE CEILING 450.13(B)
  
 3) TRANSFORMER CUT SHEET. NEEDED.
  
 4) TRANSFORMER NOT IN A ROOM? 450.21(B)
  
 PAGE E301
  
 1) PLEASE INDICATE WHICH OUTLETS WILL BE GFCI 210.8(B)
 KITCHEN 15 AND 20A RECEPTACLES TO BE GFCI PROTECTED.