Plan Review Notes
Plan Review Notes For Permit 19091166
Permit Number 19091166
Review Stop B
Sequence Number 1
Notes
Date Text
2019-11-05 14:58:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19091166
 ADD: 700 S. ROSEMARY AVE. # 112
 CONT: TBD/ TO BE DETERMINED
 TEL: ?????????
 E-MAIL: [email protected] CONTACT: HOLLAND MARTIN
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 05/ 2019
 ACTION: DENIED
  
 1) SHEET 004_EM1.1.:
  
 1A) IN THE DINING RM. I/ 101 THE SET OF DOUBLE EGRESS
 DOORS ARE IN-SWING. PLEASE REVIEW THE 2017 FBC-B
 SECTION 1010.1.2.1. DIRECTION OF SWING.
  
 1B) THE EXTERIOR PATIO I PLEASE PROVIDE ADDITIONAL
 INFORMATION ABOUT THIS ASSEMBLY AREA. DOES THIS AREA
 HAVE A CANVAS TYPE COVERING? IT WOULD APPEAR THERE IS
 AN ENCLOSURE AROUND 3 OF THE SIDES IS THERE FENCING OR
 LATTICE ON THE 3 SIDES PREVENTING EXITING ON THESE
 SIDES? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) THE CODE ANALYSIS PLEASE BREAK OUT THE DIFFERENCE
 IN FIXED SEATING (FBC-B 1004.4) WITHOUT ARM DIVIDERS TO
 BE TAKEN AT EVERY 18 INCHES OF SEAT LENGTH, (LINEAR
 FOOT) NOT SQUARE FEET. PLEASE RECALCULATE BENCH SEATING
 FOR THE DINING ROOM II, BAR DINING AND THE 3
 SEMI-CIRCULAR BANQUET SEATS, PLEASE TAKE THE LINEAR
 MEASUREMENT AT THE SEATBACK.
  
 1D) THE CODE REQUIRES US TO USE THE OCCUPANT LOAD
 FACTOR FOR THE OCCUPANT LOAD AS WELL AS FOR SIZING OF
 THE EGRESS OPENINGS, NOT THE ALLOWABLE, WORST CASE
 SCENARIO. FBC-B TABLE 1004.1.2.
  
 1E) PLEASE REVIEW DOOR 119 AND DOOR 120. THIS BUILDING
 AND MANY IN CITY PLACE WERE BUILT WITH THE MALL CONCEPT
 IN MIND. THAT BEING SAID THE BACK OF HOUSE CORRIDOR IS
 ACTUALLY AN EXIT PASSAGEWAY BOTH THE SECONDARY MEANS OF
 EGRESS DOOR 120 (FBC-B 402.8.6.1) AND THE STORAGE DOOR
 119 SERVICE AREAS FRONTING ON THE EXIT PASSAGEWAY
 (FBC-B 402.8.7) BOTH REQUIRE 1 HOUR FIRE BARRIER IN
 ACCORDANCE WITH SECTION 707 AND THE FIRE PROTECTION OF
 OPENINGS IN FIRE BARRIERS SHALL NOT BE LESS THAN 1
 HOUR, FBC-B 402.8.7, AND TABLE 716.5.
  
 2) SHEET 047_S1.0 GENERAL NOTE # 1 INDICATES THE
 STRUCTURAL DESIGN IS TO THE 2015 FLORIDA CONSTRUCTION
 CODE. PLEASE UPDATE THE PLANS TO THE 2017 FLORIDA
 BUILDING CODE- BUILDING.
  
 3) THE STRUCTURAL SHEETS SHOW VARIOUS DETAILS WHERE
 EITHER BOLTED OR WELDED CONNECTIONS WILL BE REQUIRED.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 4A) THE DOOR SCHEDULE SHEET A9.1 INDICATED THE
 INSTALLATION OF NEW EXTERIOR DOORS WITH THE FLORIDA
 APPROVAL NUMBER FL 7237.2 PLEASE UPLOAD THE FLORIDA
 APPROVALS TO THE SUPPORTING DOCUMENTS FILE. LOAD THE
 APPROVAL AS ONE FILE. BEFORE SUBMITTING TO THE BUILDING
 DEPARTMENT PLEASE IDENTIFY ON THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 5) WITH THE INSTALLATION OF THE NEW EXTERIOR DOORS
 PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS
 PROJECT.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 5.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6) THE STRUCTURAL SHEETS SHOW THE BRACING OF THE ROOF
 TOP FRAMING FOR NEW ROOFTOP EQUIPMENT. SHEET M1.01
 SHOWS NEW ROOFTOP EXHAUST FANS, KITCHEN EXHAUST AND
 ROOF PROTECTION SYSTEMS. SHEET M-1.02 DETAIL 19
 PROVIDES ROOF TOP CURB DETAILS, RAIL SUPPORT FOR ROOF
 TOP MECHANICAL EQUIPMENT BUT THERE ARE NO ANCHORING
 DETAILS ON EITHER THE STRUCTURAL OR MECHANICAL SHEETS
 HOW THE CURBS ARE TO BE SECURED TO BAR JOIST AND
 ADDITIONAL ROOF TOP FRAMING MEMBERS? THE PLANS ARE ALSO
 DEFICIENT OF HOW THE MECHANICAL EQUIPMENT WILL BE
 ANCHORED TO THE ROOF TOP CURBING.
 LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 7A) NEITHER THE ARCHITECTURAL SHEETS NOR MECHANICAL
 SHEETS PROVIDE SCREENING DETAILS FOR THE ROOF TOP
 EQUIPMENT OR ANCHORING OF SAID SYSTEM. 2017 FBC-B
 ? 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 7B) 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
 EXCEPTION: WHERE LOCATED ON BUILDINGS OF TYPE IA
 CONSTRUCTION, THE HEIGHT OF MECHANICAL EQUIPMENT
 SCREENS SHALL NOT BE LIMITED.
  
 8) SHEET A3.1 SHOWS THE EXISTING AND NEW ROOFTOP
 EQUIPMENT BUT NOT HOW TO GAIN ACCESS TO THE ROOF TOP
 EQUIPMENT. PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION:
 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES HIGH OR WALKING ON ROOFS HAVING
 A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS
  
 9) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  