| 2019-10-10 15:34:24 | 1ST REVIEW: 19091159 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P-1 PAGE IS TO CONGESTED TO DETERMINE CODE |
| | COMPLIANCE PLEASE SEPARATE THE THE SANITARY ISOMETRIC |
| | DRAWING FROM THE FLOOR PLAN. PER WPB AMEND TO FBC |
| | 107.3.5.3(12) |
| | |
| | 2. SHT P-1 THE SANITARY RISER IS NOT CODE COMPLIANT |
| | PLEASE CORRECT THE FOLLOWING ISSUES. |
| | A)THE 3" VENT IN ALL THREE BATHROOM GROUPS APPEARS TO |
| | BE A HORIZONTAL DRY VENT WHICH IS NOT ALLOWED BY CODE |
| | THESE VENT ARE NOT REQUIRED VENTS THE VENTS ON THE |
| | LAVATORY CAN SERVE AS THE VENT FOR THE BATHROOM GROUP. |
| | PER FBC RES P3108.1 |
| | B) THE LAVATORY IN BATHROOM #2 SHALL CONNECT BETWEEN |
| | THE TOILET AND THE SHOWER TO CREATE A CODE COMPLIANT |
| | WET VENT SYSTEM. PER FBC RES P3108.1 |
| | |
| | 3. PLEASE PROVIDE SIZING CALCULATIONS FOR ROOF DRAINS . |
| | PER WPB AMEND TO FBC 107.2.1 SHALL COMPLY WITH FBC RES |
| | R903.4.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |