| 2019-11-25 11:53:51 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19091122 |
| | 11/25/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | SHEETS M3, P3, & E3 HAVE NOT BEEN CORRECTED. THE |
| | STORAGE MEZZANNE IS STILL IDENTIFIED AS AN ATTIC- SEE |
| | COMMENT BELOW. |
| | |
| | 1) SHEET M-3: THE EXISTING STORAGE MEZZANINE IS NOW |
| | IDENTIFIED AS AN "ATTIC". PLEASE SEE SECTION 202 FBC EC |
| | WHICH DEFINES ATTICS AS ENCLOSED UNCONDITIONED SPACES |
| | ABOVE CEILINGS. THIS AREA IS CONDITIONED, IT'S SQUARE |
| | FOOTAGE HAS BEEN ADDED TO THE REVISED ENERGY |
| | CALCULATIONS (TOTAL 11208 SF), AND THE REVISED AC |
| | CALCULATION FOR RTU- 2 INDICATES VENTILATION CFMS FOR |
| | OCCUPANTS. PLEASE CLARIFY THE USE OF THE SPACE, AND |
| | CORRECT THE IDENTIFICATION ON THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |