| 2019-10-21 16:31:25 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19091122 |
| | REVIEWED: OCTOBER 21, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 505 FBC[EXISTING]PLEASE CHANGE LEVEL OF ALTERATION |
| | TO LEVEL 3 ON SHEET ALS1.1 SINCE ALTERATIONS OCCUR IN |
| | MORE THAN 50% OF THE BUILDING AREA. |
| | |
| | 2) 501 GENERAL AREA. |
| | THE SQ. FOOTAGE VARIES FROM PAPA AT 9792, SHEET ALS1.1 |
| | AT 9140 AND ENERGY CALCS AT 10,979. PLEASE GIVE AN |
| | OVERALL SQ. FOOTAGE FOR AREA CALCULATION. THE AREA SQ. |
| | FOOTAGE CAN EXCLUDE THE MEZZANINE IF IT MEETS THE |
| | REQUIREMENTS (SEE COMMENTS 4 AND 5). THE LIFE SAFETY |
| | OCCUPANCY SQ. FOOTAGE CAN REMAIN AS SHOWN ON SHEET |
| | ALS1.1. |
| | ADJUST SQ. FOOTAGE ON ENERGY CALCS IF APPLICABLE. |
| | ALSO, THE ENERGY CALCULATIONS INCLUDE NO INPUT DATA FOR |
| | FLOORS, WALLS, WINDOWS, DOORS, SKYLIGHTS AND ROOF. I |
| | HAVE NO DATA FOR INSULATION ON ROOF OR WALLS. PLEASE |
| | PROVIDE DATA FOR BUILDING ENVELOPE. |
| | |
| | 3) TABLE 506.2 ALLOWS 9000 SQ. FT. FOR OCCUPANCY B TYPE |
| | V-B CONSTRUCTION. IT APPEARS THAT YOU WOULD LIKE THE |
| | MEZZANINE TO NOT COUNT TOWARDS THAT SQUARE FOOTAGE |
| | LIMIT, SO PLEASE SHOW DETAILS THAT THE MEZZANINE MEETS |
| | ALL CRITERIA FOR A MEZZANINE. |
| | |
| | 4) 505.2 MEZZANINES. A MEZZANINE OR MEZZANINES IN |
| | COMPLIANCE WITH SECTION 505.2 SHALL BE CONSIDERED A |
| | PORTION OF THE STORY BELOW. SUCH MEZZANINES SHALL NOT |
| | CONTRIBUTE TO EITHER THE BUILDING AREA OR NUMBER OF |
| | STORIES AS REGULATED BY SECTION 503.1. THE AREA OF THE |
| | MEZZANINE SHALL BE INCLUDED IN DETERMINING THE FIRE |
| | AREA. THE CLEAR HEIGHT ABOVE AND BELOW THE MEZZANINE |
| | FLOOR CONSTRUCTION SHALL BE NOT LESS THAN 7 FEET (2134 |
| | MM). |
| | -WHAT IS THE CEILING HEIGHT IN MEZZANINE AREA? |
| | |
| | 5) 505.2.3 OPENNESS. A MEZZANINE SHALL BE OPEN AND |
| | UNOBSTRUCTED TO THE ROOM IN WHICH SUCH MEZZANINE IS |
| | LOCATED EXCEPT FOR WALLS NOT MORE THAN 42 INCHES (1067 |
| | MM) IN HEIGHT, COLUMNS AND POSTS. |
| | -IS THE MEZZANINE OPEN TO THE AREA THAT IT SERVES? |
| | PLEASE SHOW DETAILS OF WHAT THE INTERIOR WALL CONSISTS |
| | OF ON THE MEZZANINE LEVEL. I SEE A DETAIL FOR MEZZANINE |
| | RAILING ON A3.1.2, BUT I DON?T SEE IT CALLED OUT ON |
| | PLANS. |
| | |
| | PROVISOS: |
| | A)DEFERRED SUBMITTALS-INTERIOR GLASS WALL SYSTEM, |
| | ROOFING(WITH SUB-PERMIT APPLICATION) AND SKYLIGHTS |
| | B)SEPARATE PERMITS REQUIRED FOR- |
| | LOW VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION. |
| | C) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE |
| | PLANS AT FINAL STAMPING. |
| | |
| | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |