| Date |
Text |
| 2019-11-13 14:00:12 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19091106 |
| | 11/13/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET H-1: THE CONTRACTOR OR DESIGNER OF RECORD |
| | SHALL PROVIDE A TITLE BLOCK AND SIGNATURE ON THE |
| | MECHANICAL PLAN SHEET H-1- SECTION 107.2.1 WPB. IF THE |
| | DESIGNER IS A FL. LICENSED ARCHITECT OR ENGINEER, |
| | HE/SHE SHALL ALSO PROVIDE AN ORIGINAL SEAL AND WET |
| | SIGNATURE PER FL. STATUTES 481.221, 471.025, AND |
| | SECTIONS 61G1-16.003 AND 61G15-23.002 FAC. |
| | A) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS |
| | REQUIRED: SEE FLORIDA STATUTE 633.021, AND SECTION |
| | 107.2.1 WPB AMENDMENTS TO THE FBC. ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL |
| | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. |
| | |
| | 2) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLAN |
| | INDICATING MAKES AND MODELS, COOLING AND HEATING |
| | CAPACITIES, ENERGY EFFICIENCY RATINGS, TOTAL SUPPLY |
| | CFMS, AND ELECTRICAL DATA- SECTION 107.2.1 WPB |
| | |
| | 3) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION R403.6.1 FBC EC. |
| | |
| | 4) SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR |
| | THE NEW HOME- SECTION R101.5.1 FBC EC. |
| | |
| | 5) H-1: EXHAUST VENTILATION AT A RATE OF 100 CFMS |
| | INTERMITTENT OR 25 CFMS CONTINUOUS SHALL BE PROVIDED |
| | FOR THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE |
| | SECTION M1503.1 FOR RANGE HOOD REQUIREMENTS, AND |
| | M1503.4 FOR MAKEUP AIR. |
| | |
| | 6) H-1: AHU-2- PROVIDE THE FLEX DUCT SIZES FROM THE |
| | DISTRIBUTION BOX TO THE BEDROOMS AND THE CABANA- |
| | SECTION M1601.4 FBC RES. |
| | |
| | 7) H-1 VERIFY COMPLIANCE WITH SECTION R403.3.6 FBC RES- |
| | AIR-HANDLING UNITS IN ATTICS: |
| | |
| | AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC |
| | WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION |
| | R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR |
| | COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | |
| | 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| | 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| | |
| | 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN |
| | THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| | PROPERLY. |
| | |
| | 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| | REPLACE THE AIR HANDLER. |
| | |
| | 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| | CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST |
| | PARAGRAPH IN BOLD: |
| | |
| | NOTICE TO HOMEOWNER |
| | A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR |
| | HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT |
| | AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM, |
| | YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. |
| | YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR |
| | BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU |
| | WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR |
| | (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE |
| | CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL |
| | DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF |
| | SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER |
| | WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF |
| | PEAK OPERATION. |
| | |
| | 8) H-1: SHOW THE LOCATIONS OF THE CONDENSERS AND |
| | PROVIDE ENGINEERING FOR INSTALLATION OF THE PAD AND |
| | MOUNTING OF THE CONDENSER- SECTIONS M1305.1.4.1 AND |
| | M1401.4 FBC RES. |
| | |
| | 9) H-1: PROVIDE A CONDENSATE DISPOSALPLAN- M1411.3 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |