Plan Review Notes
Plan Review Notes For Permit 19091112
Permit Number 19091112
Review Stop E
Sequence Number 1
Notes
Date Text
2019-11-05 06:46:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT LOW VOLTAGE SYSTEMS, GENERATORS, AND
 SWIMMING POOLS ARE NOT INCLUDED IN THE SCOPE OF THIS
 PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.
  
 2. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 3. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 4. AUTOMATIC TRANSFER SWITCH SHOWN ON PLAN BUT NOT
 REFLECTED ON ONE-LINE DIAGRAM OF SERVICE. PROVIDE
 ACCURATE ONE-LINE DIAGRAM TO INLCUDE ATS OR REMOVE ATS
 FROM PLAN. FBC 107.2.1
  
 5. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
  
 6. PANEL B SHOWS A PANEL SCHEDULE INDICATING ALL
 CIRCUITS ARE " GENERAL LIGHTING". PANEL SCHEDULE MUST
 BE MORE SPECIFIC. FBC 107.2.1
  
 7. ONE-LINE DIAGRAM SHOWS A DOUBLE-LUGGED METER CAN
 FEEDING 2-200 AMP SERVICE DISCONNECTS THEN FEEDING
 PANELS A & B WITH 2/0 CU WIRE. PER NEC 310.15(B)(7)
 WIRE SIZE MUST BE 3/0 CU. TO SERVICE DISCONNECTS AND TO
 PANELS.
 PROVIDE CORRECTION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  