| Plan Review Notes For Permit 19091105 |
| Permit Number |
19091105 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2020-03-24 15:09:08 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-REVISE ENERGY CALCULATIONS: | | | A) REVISE WINDOWS AREAS AND ORIENTATION TO MATCH PLANS. | | | B) REVISE DOORS ORIENTATION TO MATCH PLANS. | | | C) REVISE DOOR TYPE TO MATCH PLANS AND PRODUCT | | | APPROVALS. (NO WOOD) | | | | | | 2- REVISE THE DESIGN CRITERIA ON SHEET A-2. CURRENT | | | CODE IS THE 2017 NOT 2007. BUILDING EXPOSURE IS "C" NOT | | | "B". REVISE DESIGN PRESSURES ACCORDINGLY. | | | NOTE: COORDINATE WITH DESIGN CRITERIA ON SHEET A-1 |
|