| 2019-10-16 11:19:01 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM IS NOT CODE COMPLIANT. THE SERVICE |
| | CONDUCTORS MUST HAVE OVERCURRENT PROTECTION WHERE THEY |
| | ENTER THE DWELLING UNIT. SERVICE CONDUCTORS ARE NOT |
| | PERMITTED TO EXTEND FURTHER THAN 8 FEET INTO A |
| | STRUCTURE WITHOUT OVERCURRENT PROTECTION. IF THIS |
| | OVERCURRENT PROTECTION IS LOCATED ON THE EXTERIOR OF |
| | THE DWELLING, THAN THE CONDUIT TO THE INTERIOR PANEL |
| | MUST INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. IF THE |
| | CONDUCTORS ARE RUN UNDERGROUND FROM THE METER TO THE |
| | INTERIOR PANEL, AND THAT PANEL HAS A MAIN BREAKER, THE |
| | CONDUCTORS MUST NOT EXCEED 8 FEET IN LENGTH BEFORE |
| | TERMINATION TO THE MAIN BREAKER. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. NEC 230.70, 250.122; FBC RE E3601.6, |
| | E3704.6, 3607.3.1 |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 3. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS |
| | SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8(A)(9); FBC RE E3902.9 |
| | 4. NOTE 12 STATES THAT LIGHTING IN CLOTHES CLOSETS |
| | SHALL COMPLY WITH NEC 410.8, WHICH IS NOT THE CORRECT |
| | CODE. PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 |
| | 5. NOTE 18 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE E4002.14 |
| | 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |