2019-12-11 13:13:36NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- ENERGY CALCULATIONS:
 A)MISSING THE ENERGY CALCULATIONS. PROVIDE ENERGY
 CALCULATIONS (2 COPIES) AS REQUIRED BY SEC. R101.5.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS SUBMITTED:
 A) REVISE ADDRESS ON THE ENERGY CALCULATIONS TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B) NUMBER OF BEDROOMS IS INCORRECT. REVISE ITEM #4 ON
 PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4
 DOESN'T MATCH PLANS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, PERMIT OFFICE AND
 JURISDICTION SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 E) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NO DOORS N THE WEST SIDE AND THERE ARE NO WOOD
 DOORS SHOWN ON PLANS OR PRODUCT APPROVALS SUBMITTED.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 F) WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
  
 2- SURVEY SUBMITTED:
 A) FOOTPRINT OF PROPOSED RESIDENCE SHOWN ON THE SURVEY
 DOESN'T MATCH THE FOOTPRINT OF PROPOSED HOUSE. IT LOOKS
 LIKE THERE IS A MIRROR IMAGE. REVISE AS REQUIRED TO
 MATCH PROPOSED ORIENTATION. . SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: ALSO CHECK DIMENSIONS. SEE PLANS.
  
 RESPONSE:
 SURVEY SUBMITTED STILL DOESN'T MATCH ORIENTATION OF
 PLANS AND REVISE ALL DIMENSIONS TO MATCH PLANS. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 3- SEDIMENT CONTROL AND SITE IMPROVEMENT PLAN SUBMITTED
 FROM THE ENGINEERING FIRM LAST DEVENPORT, INC:
 A) THE FOOTPRINT OF THE PROPOSED HOUSE SHOWN ON THE
 PLAN DOESN'T MATCH THE FOOTPRINT OF PROPOSED HOUSE.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) REVISE DRAINAGE PLAN SUBMITTED:
 (1) SECTION A-A SHOWS LIKE A BERM ADJACENT TO THE
 PROPERTY LINE. THE THE WAY IT IS SHOWN IT LOOKS LIKE
 THE BERM IS DIVERTING THE WATER TO THE ADJACENT
 NEIGHBOR. NEED TO KEEP THE WATER WITHIN THE PROPERTY.
 REVISE AS REQUIRED.
 (2) THERE IS NO INFORMATION GIVEN FOR THE REAR OF THE
 LOT SHOWING HOW KEEPING THE WATER WITHIN THE PROPERTY.
 PROVIDE INFORMATION.
 SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS. SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NONE OF THE COMMENTS WERE ADDRESSED.
  
 4- OK
 5- OK
 6-OK
 7- OK
 8-OK
  
 9- REVISED TRUSS PACKAGE TO BE DELIVERED TO THE
 BUILDING INSPECTOR AT FRAMING INSPECTION.
  
 10- OK
  
 11-IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]