| 2019-12-11 13:13:36 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | 1- ENERGY CALCULATIONS: |
| | A)MISSING THE ENERGY CALCULATIONS. PROVIDE ENERGY |
| | CALCULATIONS (2 COPIES) AS REQUIRED BY SEC. R101.5.1 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) REVISE ADDRESS ON THE ENERGY CALCULATIONS TO MATCH |
| | PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | B) NUMBER OF BEDROOMS IS INCORRECT. REVISE ITEM #4 ON |
| | PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | C) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 |
| | DOESN'T MATCH PLANS. REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | D) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME, PERMIT OFFICE AND |
| | JURISDICTION SEC. R101.5.1.1.2 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | E) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE |
| | ARE NO DOORS N THE WEST SIDE AND THERE ARE NO WOOD |
| | DOORS SHOWN ON PLANS OR PRODUCT APPROVALS SUBMITTED. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | F) WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH |
| | PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH |
| | PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | |
| | 2- SURVEY SUBMITTED: |
| | A) FOOTPRINT OF PROPOSED RESIDENCE SHOWN ON THE SURVEY |
| | DOESN'T MATCH THE FOOTPRINT OF PROPOSED HOUSE. IT LOOKS |
| | LIKE THERE IS A MIRROR IMAGE. REVISE AS REQUIRED TO |
| | MATCH PROPOSED ORIENTATION. . SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | NOTE: ALSO CHECK DIMENSIONS. SEE PLANS. |
| | |
| | RESPONSE: |
| | SURVEY SUBMITTED STILL DOESN'T MATCH ORIENTATION OF |
| | PLANS AND REVISE ALL DIMENSIONS TO MATCH PLANS. REVISE |
| | AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | 3- SEDIMENT CONTROL AND SITE IMPROVEMENT PLAN SUBMITTED |
| | FROM THE ENGINEERING FIRM LAST DEVENPORT, INC: |
| | A) THE FOOTPRINT OF THE PROPOSED HOUSE SHOWN ON THE |
| | PLAN DOESN'T MATCH THE FOOTPRINT OF PROPOSED HOUSE. |
| | REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | B) REVISE DRAINAGE PLAN SUBMITTED: |
| | (1) SECTION A-A SHOWS LIKE A BERM ADJACENT TO THE |
| | PROPERTY LINE. THE THE WAY IT IS SHOWN IT LOOKS LIKE |
| | THE BERM IS DIVERTING THE WATER TO THE ADJACENT |
| | NEIGHBOR. NEED TO KEEP THE WATER WITHIN THE PROPERTY. |
| | REVISE AS REQUIRED. |
| | (2) THERE IS NO INFORMATION GIVEN FOR THE REAR OF THE |
| | LOT SHOWING HOW KEEPING THE WATER WITHIN THE PROPERTY. |
| | PROVIDE INFORMATION. |
| | SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY |
| | AMENDMENTS. SEC. 110.9 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NONE OF THE COMMENTS WERE ADDRESSED. |
| | |
| | 4- OK |
| | 5- OK |
| | 6-OK |
| | 7- OK |
| | 8-OK |
| | |
| | 9- REVISED TRUSS PACKAGE TO BE DELIVERED TO THE |
| | BUILDING INSPECTOR AT FRAMING INSPECTION. |
| | |
| | 10- OK |
| | |
| | 11-IMPACT FEES - |
| | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK |
| | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. |
| | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT |
| | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |