Plan Review Notes For Permit 19091074
Permit Number 19091074
Review Stop P
Sequence Number 1
Notes
Date Text
2019-10-04 06:58:321) THE PUMP THAT IS CALLED OUT ON SHT.1 IN THE POOL
 EQUIPMENT SCHEDULE IS DIFFERENT THAN THE PUMP THAT IS
 CIRCLED ON THE SUBMITTED PUMP SPECIFICATIONS. CLARIFY.
 2) SHT. 3 OF 5 - THE TOTAL DYNAMIC HEAD SECTION ON THIS
 SHEET IS ILLEGIBLE AND UNACCEPTABLE. SUBMIT A SEPARATE
 SHEET WITH THIS INFORMATION IN A CLEAR AND LEGIBLE
 FORMAT. IN ADDITION, THE TWO PUMP CURVES AND PRINTING
 ARE BLURRED AND ILLEGIBLE. WPB AMEND. TO FBC SEC.
 107.2.1. I HAVE BROUGHT THIS TO THE CONTRACTOR'S
 ATTENTION PREVIOUSLY AND EXPLAINED THAT THIS SHEET IS
 UNACCEPTABLE AND WILL BE REJECTED IF IT SUBMITTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW