| Plan Review Notes For Permit 19091074 |
| Permit Number |
19091074 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-04 06:58:32 | 1) THE PUMP THAT IS CALLED OUT ON SHT.1 IN THE POOL | | | EQUIPMENT SCHEDULE IS DIFFERENT THAN THE PUMP THAT IS | | | CIRCLED ON THE SUBMITTED PUMP SPECIFICATIONS. CLARIFY. | | | 2) SHT. 3 OF 5 - THE TOTAL DYNAMIC HEAD SECTION ON THIS | | | SHEET IS ILLEGIBLE AND UNACCEPTABLE. SUBMIT A SEPARATE | | | SHEET WITH THIS INFORMATION IN A CLEAR AND LEGIBLE | | | FORMAT. IN ADDITION, THE TWO PUMP CURVES AND PRINTING | | | ARE BLURRED AND ILLEGIBLE. WPB AMEND. TO FBC SEC. | | | 107.2.1. I HAVE BROUGHT THIS TO THE CONTRACTOR'S | | | ATTENTION PREVIOUSLY AND EXPLAINED THAT THIS SHEET IS | | | UNACCEPTABLE AND WILL BE REJECTED IF IT SUBMITTED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|