| Plan Review Notes For Permit 19091022 |
| Permit Number |
19091022 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-18 10:47:22 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1.THE BREAK ROOM SHALL HAVE A CLEARANCE OF 60" MIN | | | BETWEEN CABINETS. COMPLY WITH FBC ACC 212.2, AND | | | 804.2.2 U-SHAPED. IN U-SHAPED KITCHENS ENCLOSED ON | | | THREE CONTIGUOUS SIDES, CLEARANCE BETWEEN ALL OPPOSING | | | BASE CABINETS, COUNTER TOPS, APPLIANCES, OR WALLS | | | WITHIN KITCHEN WORK AREAS SHALL BE 60 INCHES MINIMUM. | | | | | | 2. PLEASE PROVIDE ISOMETRIC DRAWINGS FOR THE WATER AND | | | SANITARY FOR ALL NEW PLUMBING. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|