| 2019-11-15 12:27:28 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19091022 |
| | ADD: 515 N. FLAGLER DR. SUITE: 408 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL/ CONTACT: NUNEZ DARA |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. NOV. 15/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE DIGITAL PLAN SUBMITTAL DOES NOT HAVE |
| | ANY OF THE ARCHITECTURAL SHEETS DIGITALLY SIGNED AND |
| | SEALED IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 |
| | PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR |
| | ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) SHEET A0.02 THE LIFE SAFETY PLAN SHOW THE DESIGNER |
| | OF RECORD HAS ELECTED TO RATE THE CORRIDOR WALLS AND |
| | TENANT SEPARATION WALLS. THE CODE UNDER WHICH THE |
| | BUILDING WAS BUILT REQUIRED FIRE RATED CORRIDORS AND |
| | TENANT SEPARATION WALLS. UNDER THE CURRENT CODE (2017 |
| | FBC-B 6TH EDITION) FOR A BUILDING (HIGHRISE) WITH A |
| | BUSINESS OCCUPANCY, FIRE SPRINKLERED, THERE IS NO |
| | REQUIREMENT FOR 1 HOUR FIRE RATED CORRIDORS, FOR THIS |
| | REASON THE ENTRY DOORS DO NOT REQUIRE A FIRE RATING. |
| | I?VE SPOKEN WITH THE BUILDING OFFICIAL ROBERT BROWN |
| | ABOUT THIS ISSUE. FOR THIS PLAN AND OTHERS IN THE |
| | FUTURE WHERE THE DESIGNER OF RECORD HAS A MORE |
| | STRINGENT DESIGN THAN CODE OR IF THE BUILDING STANDARD |
| | IS HIGHER THAN THE CURRENT CODE PLEASE PLACE A NOTE ON |
| | THE PLAN PLEASE PLACE A NOTE SIMILAR TO ABOVE STATING |
| | THE DESIGN IS HIGHER THAN THE CURRENT CODE AND |
| | REFERENCE THE CURRENT CODE WITHIN THE NOTE. THIS WILL |
| | HELP IN YEARS TO COME WHEN SOMEONE MAY QUESTION WHY THE |
| | DOORS AREN?T RATED. WE THANK YOU FOR YOUR HELP IN THIS |
| | MATTER. |
| | |
| | 3) SHEET A0.03 UL DETAILS: |
| | 3A) THIS SHEET DOES NOT SHOW A METAL STUD ONE HOUR |
| | RATED WALLS SYSTEM. THE PLAN SHOW A ONE HOUR BLOCK WALL |
| | ASSEMBLY DETAIL # 4 AND A NON-RATED METAL STUD ASSEMBLY |
| | DETAIL # 8. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. IF THE DESIGNER DESIGNS TO A STRICTER |
| | STANDARD OR IF THE BUILDING STANDARD IS STRICTER THAN |
| | THE CODE REQUIREMENT, THEN YOU WOULD STILL NEED TO SHOW |
| | HOW COMPLIANCE WITH FIRE PARTITIONS/ 708.3 FIRE |
| | RESISTANCE RATING. |
| | |
| | 3B) DETAIL # 7 INDICATES A PRE-FABRICATED LIGHT GAUGE |
| | STEEL TRUSS FLOOR TRUSS SYSTEM. PLEASE PROVIDE THE |
| | CORRECT FLOOR SYSTEM FOR THE BUILDING. THIS BUILDING |
| | HAS EITHER A 6 INCH OR 8 INCH POST STRESSED FLOOR |
| | SYSTEM, PLEASE UPDATES THE PLANS AND FLOOR SYSTEM. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) BUILDING PROVISO: SHEET A4.21 INTERIOR ELEVATIONS |
| | DETAIL # 7 SHOWS 2 MICROWAVES. AT THE TIME OF FINAL |
| | INSPECTION THE MICROWAVE ON THE COUNTER HAS TO BE IN |
| | PLACE TO MEET THE ACCESSIBILITY REQUIREMENTS OF THE |
| | 2017 FBC-ACCESSIBILITY CODE SECTIONS: |
| | 4A) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 4B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS |
| | SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | MAXIMUM. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |