| 2019-09-26 11:47:32 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19091009 |
| | 9/26/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MS.0.1: CONCERNING THE CONDENSING UNITS SHOWN |
| | IN THE INTERIOR OF THE BUILDING, PLEASE REFER TO |
| | COMMENT #15 FROM THE 1ST MECHANICAL REVIEW ON THE MAIN |
| | BUILDING PERMIT #17110075. IN RESPONSE TO THE COMMENT, |
| | THE ARCHTITECT REQUESTED A DEFERRED SUBMITTAL TO |
| | PROVIDE MANUFACTURER'S CERTIFICATION OF THE OUTDOOR |
| | UNITS BEING INSTALLED IN THE INTERIOR OF THE BUILDING. |
| | TO DATE THERE HAS NOT BEEN A SUBMITTAL PROVIDED TO |
| | ADDRESS THE ISSUE. PLEASE NOTE AC CONDENSERS SHALL BE |
| | INSTALLED OUTDOORS IN ACCORDANCE WITH THEIR LISTING AND |
| | MANUFACTURER'S SPECIFICATIONS - SECTION 304.1 FBC M. |
| | |
| | 2) MS.0.1: ASSUMING THE CONDENSERS ARE APPROVED BY THE |
| | MANUFACTURER TO BE INSTALLED ON THE INTERIOR AS SHOWN |
| | ON THE PLAN, PLEASE SHOW THE REFRIGERANT PIPING RUNS TO |
| | THE FROM THE CU'S TO THE AIR HANDLERS- SECTION 107.2.1 |
| | WPB. |
| | |
| | 3) MS.0.1: SHOW THE LOCATION OF THE AIR HANDLER |
| | SUPPLYING THE SMALL OFFICES, COPY ROOM, AND THE |
| | MEZZANINE- SECTION 107.2.1 WPB. |
| | |
| | 4) MS.0.1: PLEASE PROVIDE AN AC EQUIPMENT SCHEDULE ON |
| | THE PLAN- SECTION 107.2.1 WPB. |
| | |
| | 5) MS.0.1: THE NEW DDCV DOOR OPENING FROM THE |
| | FIRE-RATED STAIRWAY EXTENSION INTO THE ROOM IS NOT |
| | ALLOWED PER SECTION1023.3.1 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |