| Date |
Text |
| 2019-09-27 09:43:15 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE DRINKING FOUNTAINS ARE NOT ALLOWED TO BE |
| | INSTALLED IN THE EXIT PASSAGEWAY. FBC 1024.1 EXIT |
| | PASSAGEWAYS. EXIT PASSAGEWAYS SERVING AS AN EXIT |
| | COMPONENT IN A MEANS OF EGRESS SYSTEM SHALL COMPLY WITH |
| | THE REQUIREMENTS OF THIS SECTION. AN EXIT PASSAGEWAY |
| | SHALL NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS |
| | OF EGRESS AND A CIRCULATION PATH. FBC 1024.6 |
| | PENETRATIONS. PENETRATIONS INTO OR THROUGH AN EXIT |
| | PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT AND |
| | DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION, |
| | SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR |
| | FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY |
| | SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL |
| | BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTION 714. THERE SHALL NOT BE PENETRATIONS OR |
| | COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT, |
| | BETWEEN ADJACENT EXIT PASSAGEWAYS. |
| | |
| | 2) THE DOOR FROM THE BUSINESS INTO THE EXIT PASSAGEWAY |
| | THROUGH THE 2 HOUR FIRE RATED BARRIER WALL IS REQUIRED |
| | TO TO HAVE A 90 MINUTE FIRE RATING. FBC TABLE 716.5 |
| | |
| | 3) THERE ARE ERRORS IN THE CODE DATA ON SHEET LS-1. THE |
| | DATA FOR THIS PROJECT SHOULD MATCH THE SHELL BUILDING |
| | DATA. |
| | A) AREA (TABLE 506.2) HAS UNLIMITED AREA FOR A BUSINESS |
| | AND STORAGE OCCUPANCIES IN A FULLY SPRINKLERED BUILDING |
| | OF TYPE 1B CONSTRUCTION. |
| | B) FIRE-RESISTANCE RATING REQUIREMENTS (TABLE 601) ARE |
| | FOR TYPE VB CONSTRUCTION AND THIS IS A 10 STORY |
| | BUILDING OF TYPE 1B CONSTRUCTION. |
| | |
| | 4) FINISH PLAN NOTES #1 ON SHEET A2.1 STATES "REFER TO |
| | SHEET A-1.5 FOR FINISH SPECIFICATIONS". THERE IS NO |
| | SHEET A-1.5 IN THE SHEET INDEX OR ON THE PLANS. FBC |
| | 107.2.1 |
| | |
| | 5) ACCESSIBLE SEATING IS REQUIRED AT THE FIXED CENTER |
| | COUNTER AND THE FIXED BENCH SEATING AREA PER FBC |
| | ACCESSIBILITY 902.1 AND 903.1. SEE SHEET A4.1. |
| | |
| | 6) THE RECEPTION SERVICE COUNTER IS REQUIRED TO COMPLY |
| | WITH FBC ACCESSIBILITY 904.4 |
| | |
| | 7) SHOW THAT DOOR #125 TO THE WOMEN'S BATHROOM COMPLIES |
| | WITH FBC ACCESSIBILITY 404.2.4.1 FOR MANEUVERING |
| | CLEARANCES OR FRONT APPROACH ON THE PULL SIDE. |
| | |
| | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |