| 2019-10-03 16:43:02 | |
| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19091006 |
| | 10/3/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE CONVERSION OF THE EXERCISE ROOM INTO A SIXTH |
| | BEDROOM RESULTS IN THE PROJECT BEING CLASSIFIED AS A |
| | CHANGE OF OCCUPANCY- FROM R-3 TO R-4. CORRECT THE LEVEL |
| | 2 PROJECT CLASSIFICATION ON SHEET A-0.00, AND THE |
| | OCCUPANCY CLASSIFICATION. PLEASE NOTE THAT THE ORIGINAL |
| | GROUP HOME PROJECT DESIGNED UNDER THE FBC R AND |
| | APPROVED UNDER PERMIT #15040220 IS LIMITED TO FIVE |
| | PERSONS PER SECTION 310.5.1 FBC B. |
| | |
| | 2) REFER TO SECTION 1009.1 FBC-17 EXISTING BUILDING |
| | CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR |
| | ALL ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 |
| | MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE |
| | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 3) DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY AIR |
| | SYSTEMS OF EACH OF THE 5-TON AC SYSTEMS PER SECTION |
| | 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| | APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE |
| | THE SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS |
| | OF SUPPLY AIR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |