| 2019-10-09 17:47:22 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. AIC RATING OF SERVICE DISCONNECT AND PANEL |
| | FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| | SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| | FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| | NOT LESS THAN 10,000 AMPERES. (110.9) |
| | |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| | |
| | 2. THE 3-2/0 SERVICE CONDUCTORS SUPPLYING TWO 150 AMP |
| | PANEL IS UNDERSIZED. SERVICE CONDUCTORS SHALL BE SIZED |
| | PER TABLE 310.15 (B) (16). |
| | |
| | 3. LOAD CALC'S FOR EACH PANEL IS INCOMPLETE. LOAD |
| | CALC'S SHALL BE CALCULATED PER TABLE E3602.2 INCLUDE 3 |
| | VA PER SQ/FT AND SEPERATE WASHER AND DRYER LOADS. |
| | |
| | 4. SPECIFY EQUIPMENT GROUNDING CONDUCTOR BETWEEN FEEDER |
| | AND EACH PANEL PER E3704.6. |
| | |
| | 5. GROUNDING ELECTRODE SYSTEM SHALL BE PER E3608.4. |
| | DEMONSTRATE ACCESS TO EXISTING WATER PIPE OR FOOTING |
| | STEEL OR PROVIDE TWO GROUND RODS. |
| | |
| | 6. PROVIDE INTER SYSTEM BONDING CONNECTION PER E3609.3. |
| | |
| | 7. CEILING MOUNTED LUMINAIRE CLEARANCES IN CLOSETS |
| | SHALL COMPLY WITH E4003.12. |
| | |
| | 8. OUTLETS SHALL BE PROVIDED AT FRONT AND REAR OF |
| | STRUCTURE PER E3901.7. |
| | |
| | 9. PROVIDE SERVICE OUTLETS FOR A/C CU'S PER E3901.12. |
| | |
| | 10. EXISTING FIREPLACE REQUIRES CARBON MONOXIDE |
| | DETECTORS PER R315.1. |
| | |
| | 11. OUTLETS REQUIRED NEXT TO BATHROOM BASINS PER |
| | E3901.6. |
| | |
| | 12. CIRCUTS 18 & 20 AT 1ST PANEL INDICATES 14 AMP |
| | BREAKERS. BREAKER SIZING SHALL BE PER E3705.6. |
| | |
| | 13. AFCI PROTECTION SHALL BE PER E3902.16. A NOTE ON |
| | THE PLAN WILL SUFFUCE. |
| | |
| | 14. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF |
| | THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES |
| | SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT |
| | OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |