| 2019-11-06 15:17:15 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19090882 |
| | 11/5/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M-301 & M-501: IT APPEARS AHU & CU 1-7 HAVE |
| | BEEN MISLABELED AS AHU & CU 1-2 ON THE FLOOR PLAN |
| | LAYOUT- PLEASE CORRECT. |
| | |
| | 2) M-501: PROVIDE O/A CALCULATIONS FOR THE NEW RETAIL |
| | AC SYSTEM- TABLE 403.3.1.1 FBC M. |
| | |
| | 3) M-310: VERIFY THE RETAIL O/A INTAKE LOCATION IS IN |
| | COMPLIANCE WITH SECTION 401.4 FBC M FOR REQUIRED |
| | CLEARANCES. |
| | |
| | 4) M-303: A FIRE/SMOKE DAMPER IS REQUIRED AT THE |
| | PENETRATION OF THE 12X12 OA DUCT INTO THE SHAFT PER |
| | 607.5.5 FBC M. |
| | |
| | 5) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE FIRE DAMPERS AND |
| | FIRE/SMOKE DAMPERS (IF REQUIRED). THE SPECS MAY BE |
| | DEFERRED SUBMITTALS PER SECTION 107.3.4.1 WPB. |
| | |
| | 6) M-301: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE |
| | NEW RETAIL AHU- SECTION 307.2.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |