| 2019-11-18 15:29:47 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19090882 |
| | REVIEWED: NOVEMBER 18, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 404.6 FBC[B]ENCLOSURE OF ATRIUMS. ATRIUM SPACES |
| | SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR |
| | FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 707 |
| | OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH. |
| | HOW ARE BOTH LEVELS OF ATRIUM SEPARATED FROM ADJACENT |
| | SPACES? THE LIFE SAFETY PLAN SHOW A DASH DOT LINE ON |
| | THE FIRST FLOOR THAT MAY REPRESENT 1 HOUR RATING, BUT |
| | IT IS NOT DENOTED WHAT THE LINE REPRESENTS. |
| | ALSO, IT WAS DISCUSSED IN A MEETING ABOUT FIRE CURTAINS |
| | AT THE 2 ND FLOOR OPENINGS. |
| | HOW IS THE SECOND LEVEL SEPARATED AS REQUIRED IN 404.6? |
| | |
| | 2) 716.5 FBC TABLE[B]OPENING FIRE PROTECTION |
| | ASSEMBLIES, RATINGS AND MARKINGS. |
| | PLEASE LIST FIRE RATING OF ALL EXISTING DOORS IN RATED |
| | WALLS AND SHAFTS. |
| | ALSO, PROVIDE SPECIFICATIONS FOR ANY FIRE CURTAINS |
| | BEING INSTALLED, OR INDICATE THAT THEY WILL BE A |
| | DEFERRED SUBMITTAL. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |