| 2019-10-29 10:38:16 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19090864 |
| | 10/29/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY FORM R405-2017 APPEARS TO BE PROVIDING |
| | INCOMPLETE INFORMATION FOR THE APARTMENTS. REFER TO |
| | SECTIONS R405.4.2 & R405.4.2.1 FBC EC: |
| | |
| | A) PROVIDE THE STREET ADDRESS OF THE PROJECT. |
| | |
| | B) CORRECT THE "SINGLE-FAMILY" DESIGNATION TO |
| | "MULTI-FAMILY", |
| | |
| | C) CORRECT THE NUMBER OF BEDROOMS. |
| | |
| | D) THE FORM INDICATES NOT A "WORST CASE" COMPLIANCE |
| | WHICH WOULD MEAN THAT THE COMPLIANCE DATA IS ONLY |
| | RELAVENT TO ONE APARTMENT. PLEASE NOTE THAT THE AC |
| | CALCULATIONS ARE USING A BLOCK LOAD METHOD FOR SYSTEM |
| | SIZING BASED ON SECTION C407.5.2.3 FBC EC. SYSTEM |
| | SIZING USING THIS METHOD IS PERMITTED ONLY FOR |
| | MULTI-FAMILY BUILDINGS EXCEEDING THREE STORIES. |
| | |
| | E) THE THERMAL ENVELOPE FOR THE 2ND FLOOR APARTMENTS |
| | OVER THE UNCONDITIONED, UNFINISHED FUTURE RETAIL SPACES |
| | IS INCOMPLETE BECAUSE NO FLOOR/CEILING INSULATION HAS |
| | BEEN PROVIDED- SEE SHEET A.3.2.3. |
| | |
| | 2) THE AC CALCULATIONS APPEAR TO BE USING A BLOCK LOAD |
| | METHOD FOR SYSTEM SIZING BASED ON SECTION C407.5.2.3 |
| | FBC EC. SYSTEM SIZING USING THIS METHOD IS PERMITTED |
| | ONLY FOR MULTI-FAMILY BUILDINGS EXCEEDING THREE |
| | STORIES. |
| | |
| | 3) INDICATE HOW VENTILATION WILL BE PROVIDED FOR THE |
| | BIKE STORAGE 106 , AND STORAGE ROOMS 109 AND 111- |
| | SECTION 401.2 FBC M. |
| | |
| | 4) REFER TO SECTION R403.6.2 VENTILATION AIR AND |
| | PROVIDE CALCULATIONS TO INDICATE THE DESIGN AIR CHANGES |
| | PER HOUR SHALL BE THE MAXIMUM RATES ALLOWED PER |
| | RESIDENTIAL APPLICATIONS INDICATED IN THE ASHRAE 62.2 |
| | |
| | 5) SHEET M.4.3.3: THE LOCATION OF THE AC CLOSET LOUVER |
| | DOOR RETURN APPEARS TO BE WITHIN 10' OF THE RANGE WHICH |
| | IS NOT ALLOWED PER SECTION 601.5 (7) EXCEPTION 1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |