Plan Review Notes
Plan Review Notes For Permit 19090862
Permit Number 19090862
Review Stop P-GREASE
Sequence Number 2
Notes
Date Text
2019-12-12 11:52:191) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE GREASE INTERCEPTOR PER 2017 FBC-PLUMBING SEC.
 1003.2 THAT ARE IN COMPLIANCE WITH ONE OF THE LISTED
 STANDARDS IN 2017 FBC-PLUMBING SEC.1003.3.4. THERE IS A
 SIZING TABLE ON SHT.P-6.2.1 THAT IS BASED ON PIPE
 DIAMETER AND SLOPE BUT THERE IS NO REFERENCE AS TO WHAT
 STANDARD THIS IS FROM AND THEREFORE IS UNACCEPTABLE.
 2) SHT.P-5.2.1 SHOWS A ZURN GREASE INTERCEPTOR AND
 DETAILS HAVE ALSO BEEN SUBMITTED FOR SCHIER UNITS.
 IDENTIFY THE SCHIER UNITS ON SHT.P-5.2.1. TO AVOID
 CONFUSION IN THE FIELD. WPB AMEND. TO FBC-PLUMBING SEC.
 107.2.1.
 3) SUBMIT INSTALLATION MANUALS FOR THE SCHIER AND ZURN
 GREASE INTERCEPTORS AND ALSO FOR HE STRIEM SOLIDS
 INTERCEPTOR. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692