| Notes |
| Date |
Text |
| 2019-12-12 11:52:19 | 1) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR | | | THE GREASE INTERCEPTOR PER 2017 FBC-PLUMBING SEC. | | | 1003.2 THAT ARE IN COMPLIANCE WITH ONE OF THE LISTED | | | STANDARDS IN 2017 FBC-PLUMBING SEC.1003.3.4. THERE IS A | | | SIZING TABLE ON SHT.P-6.2.1 THAT IS BASED ON PIPE | | | DIAMETER AND SLOPE BUT THERE IS NO REFERENCE AS TO WHAT | | | STANDARD THIS IS FROM AND THEREFORE IS UNACCEPTABLE. | | | 2) SHT.P-5.2.1 SHOWS A ZURN GREASE INTERCEPTOR AND | | | DETAILS HAVE ALSO BEEN SUBMITTED FOR SCHIER UNITS. | | | IDENTIFY THE SCHIER UNITS ON SHT.P-5.2.1. TO AVOID | | | CONFUSION IN THE FIELD. WPB AMEND. TO FBC-PLUMBING SEC. | | | 107.2.1. | | | 3) SUBMIT INSTALLATION MANUALS FOR THE SCHIER AND ZURN | | | GREASE INTERCEPTORS AND ALSO FOR HE STRIEM SOLIDS | | | INTERCEPTOR. 2ND REQUEST. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|