2019-10-30 08:43:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL L AND H LOADS SHOWN IN PANEL MDP ARE DIFFERENT
 THAN WHAT IS SHOWN IN THE PANEL SCHEDULES FOR THOSE
 PANELS. DEMAND LOAD SHOULD BE SHOWN. PROVIDE
 CLARIFICATION/CORRECTION TO LOAD CALCULATION. NEC 220;
 WPB FBC 107.2.1
 2. AIC CALCULATION PROVIDED APPEARS TO BE FOR ONLY ONE
 OF THE SERVICE FEEDERS. PROVIDE AVAILABLE FAULT CURRENT
 FOR ALL SERVICES ON PLAN. NEC 110.3, 110.9, 110.10; WPB
 FBC 107.2.1
 3. METER CENTER LOAD CALCULATION STATES THAT THE UNIT
 PANELS HAVE A 150 AMP TRIP BREAKER FEEDING THE PANELS.
 THE RISER DIAGRAM SHOWS 125 AMP TRIP, AND THE PANELS
 ARE SHOWN AS 125 AMP RATED. PROVIDE CLARIFICATION AND
 CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5
 4. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved