| 2019-10-30 08:43:33 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PANEL L AND H LOADS SHOWN IN PANEL MDP ARE DIFFERENT |
| | THAN WHAT IS SHOWN IN THE PANEL SCHEDULES FOR THOSE |
| | PANELS. DEMAND LOAD SHOULD BE SHOWN. PROVIDE |
| | CLARIFICATION/CORRECTION TO LOAD CALCULATION. NEC 220; |
| | WPB FBC 107.2.1 |
| | 2. AIC CALCULATION PROVIDED APPEARS TO BE FOR ONLY ONE |
| | OF THE SERVICE FEEDERS. PROVIDE AVAILABLE FAULT CURRENT |
| | FOR ALL SERVICES ON PLAN. NEC 110.3, 110.9, 110.10; WPB |
| | FBC 107.2.1 |
| | 3. METER CENTER LOAD CALCULATION STATES THAT THE UNIT |
| | PANELS HAVE A 150 AMP TRIP BREAKER FEEDING THE PANELS. |
| | THE RISER DIAGRAM SHOWS 125 AMP TRIP, AND THE PANELS |
| | ARE SHOWN AS 125 AMP RATED. PROVIDE CLARIFICATION AND |
| | CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5 |
| | 4. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING |
| | PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK |
| | IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY |
| | OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |