| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | 1.FBC B 107.2.1. PLEASE CORRECT THE FOLLOWING; ON THE |
| | SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| | ASSEMBLIES: COLUMN HEADING ?ANCHOR SPACING?; VERIFY |
| | INFORMATION FROM PAGE 12 AND 13 OF PRODUCT APPROVAL |
| | FL1850; YOU MUST ALSO MULTIPLY THE ANCHOR SPACING GIVEN |
| | FOR USING ANCHOR TYPE TAPPER + BY THE FACTOR OF .51 |
| | FROM PAGE 13 EDGE DISTANCE VERSUS SPACING SCHEDULE FOR |
| | ANCHORS TO ACHIEVE THE CORRECT ANCHOR SPACING |
| | |