2019-10-03 09:48:151) SUBMIT TWO COPIES OF A POOL PUMP CURVE. IDENTIFY ON
 THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP
 BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM
 THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS.
 2) INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL PUMP.WPB AMEND. TO FBC SEC.
 107.2.1.
 4) SHT. 3 - THE WALL VACUUM FITTING SHALL BE LOCATED NO
 GREATER THAN 12 INCHES BELOW THE WATER LEVEL. APSP 7
 SEC. 4.6.
  