Plan Review Notes
Plan Review Notes For Permit 19090844
Permit Number 19090844
Review Stop M
Sequence Number 1
Notes
Date Text
2020-09-19 12:32:23PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 MECHANICAL REVIEW DENIED:
  
 1) FBC B 107.2.1, PLAN SHEET A-3 INDICATES TWO
 MINI-SPLIT AIR HANDLERS (2) ZONES. THIS DOES NOT MATCH
 MECHANICAL SHEET M-1 WHICH INDICATES ONLY ONE AIR
 HANDLER (1) ZONE FOR THE MINI-SPLIT SYSTEM. PROVIDE
 MATCHING PLAN SHEETS FOR AIR HANDLERS.
  
 PROVISO:
 FBC B 107.2.1 & FBC R M 1506.2, THE BATHROOM EXHAUST
 FAN (50 CFM) NEEDS TO BE SUFFICIENT TO MEET THE MINIMUM
 50 CFM .25 STATIC PRESSURE EXHAUST SYSTEM REQUIREMENT.
  