| Date |
Text |
| 2019-10-02 15:16:24 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT A COPY OF THE WRITTEN APPROVAL FROM THE PALM |
| | BEACH COUNTY HEALTH DEPARTMENT FOR THE POOL RESURFACING |
| | AS REQUIRED BY FAC 64E-9.005. BEFORE A POOL RESURFACING |
| | PERMIT CAN BE ISSUED A POOL RESURFACING NOTIFICATION |
| | FORM THAT HAS BEEN REVIEWED AND APPROVED BY THE PALM |
| | BEACH COUNTY HEALTH DEPARTMENT IS REQUIRED TO BE |
| | SUBMITTED. |
| | |
| | 2) RESURFACING THE POOL INTERIOR TO ORIGINAL NON-TOXIC |
| | SLIP-RESISTANT AND SMOOTH SPECIFICATIONS OR EQUIVALENT |
| | REPLACEMENT OF EQUIPMENT ARE NOT CONSIDERED |
| | MODIFICATIONS. HOWEVER, THE FOLLOWING ITEMS SHALL BE |
| | ADDRESSED DURING RESURFACING PROJECTS: |
| | (A) THE LIP OF THE GUTTER MUST BE LEVELED TO WITHIN 1/4 |
| | INCH BETWEEN THE HIGHEST AND LOWEST POINT AND THE |
| | DOWNWARD SLOPE FROM THE LIP TO THE DRAIN MUST BE |
| | MAINTAINED AS ORIGINALLY DESIGNED OR INCREASED, BUT |
| | SHALL |
| | NOT EXCEED NEW CONSTRUCTION STANDARDS. |
| | (B) TILE STEP MARKINGS MUST BE INSTALLED MEETING THE |
| | REQUIREMENTS OF SUBPARAGRAPH 64E-9.006(1)(D)3., |
| | F.A.C. |
| | (C) WHERE APPLICABLE THE SLOPE BREAK MARKING MUST BE |
| | INSTALLED MEETING THE REQUIREMENTS OF SUBSUBPARAGRAPH |
| | 64E-9.006(1)(C)2.B., F.A.C., AND THE SAFETY LINE MUST |
| | BE INSTALLED TWO FEET BEFORE THE |
| | MARKING. |
| | (D) DEPTH MARKERS AND NO DIVING MARKERS MUST BE |
| | INSTALLED IN ACCORDANCE WITH SUBPARAGRAPH 64E- |
| | 9.006(1)(C)3., F.A.C. |
| | (E) THE POOL LADDER MUST HAVE A THREE TO SIX INCH |
| | CLEARANCE FROM THE POOL WALL. NEW CROSS BRACED |
| | LADDER(S) SHALL BE INSTALLED IN PLACE OF NON-CROSS |
| | BRACED LADDER(S) IN CONFORMANCE WITH 64E-9.006(1)(D)1. |
| | DURING A POOL RE-SURFACING |
| | (F) SHOULD RESURFACING WORKS AFFECT THE STEP RISER |
| | HEIGHTS, NO RISER SHALL EXCEED 12 INCHES AND THE |
| | INTERMEDIATE RISERS SHALL BE MADE UNIFORM. |
| | (G) WHEN FIBERGLASS IS USED TO RESURFACE A POOL ANY |
| | EXISTING TILE SHALL NOT BE COVERED BY THE FIBERGLASS |
| | FINISH. |
| | (H) THE COUNTY HEALTH DEPARTMENT SHALL BE NOTIFIED IN |
| | WRITING OF ANY PROPOSED POOL RESURFACING OR |
| | UPGRADES TO DECKING AT LEAST 10 DAYS PRIOR TO |
| | COMMENCEMENT. THE NOTIFICATION SHALL INCLUDE AN |
| | ITEMIZED LIST |
| | OF ALL PROPOSED WORK THAT IS TO BE PERFORMED, THE |
| | LICENSE NUMBER OF THE CONTRACTOR SELECTED AND SHALL |
| | INDICATE THAT ALL WORK WILL MEET THE REQUIREMENTS OF |
| | PARAGRAPHS 64E-9.005(2)(A) THROUGH (G), F.A.C. |
| | (I) UPON COMPLETION OF THE WORK THE LICENSED CONTRACTOR |
| | SHALL PROVIDE THE COUNTY HEALTH DEPARTMENT A |
| | LETTER BEARING THEIR LICENSE NUMBER WHICH CERTIFIES |
| | THAT THE WORK WAS COMPLETED IN ACCORDANCE WITH |
| | PARAGRAPHS 64E-9.005(2)(A) THROUGH (G), F.A.C. |
| | (J) RECESSED TREADS THAT PROTRUDE FROM THE POOL WALL |
| | SHALL BE REMOVED AND REPLACED WITH A CROSS BRACED |
| | LADDER OR RECONSTRUCTED TO MEET THE REQUIREMENTS OF |
| | CHAPTER 64E-9.006(1)(D)2. |