| Date |
Text |
| 2019-10-03 15:16:25 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1- THIS HOUSE WAS BUILT UNDER PERMIT #05031759. |
| | ACCORDING TO CITY RECORDS, PLANS SHOW THAT THE SECOND |
| | FLOOR WAS LEFT UNFINISHED. BASED ON CITY PLANS THERE IS |
| | DOOR LEADING FROM THE GARAGE TO THE ROOM ABOVE. |
| | OPENINGS FROM THE GARAGE TO A ROOM THAT CAN BE USED FOR |
| | SLEEPING PURPOSES IS NOT ALLOWED. REVISE PLANS AS |
| | REQUIRED. SEC. 801.3 FBC-EXISTING BUILDING AND SEC. |
| | R302.5.1 FBC-RESIDENTIAL. |
| | |
| | 2- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING |
| | TO THE SECOND FLOOR TO SHOW COMPLIANCE WITH THE OPENING |
| | PROTECTION OF SEC. 801.3 FBC-EXISTING BUILDING AND SEC. |
| | R302.5.1 FBC-RESIDENTIAL. |
| | |
| | 3- NEED TO SHOW COMPLIANCE WITH THE EGRESS REQUIREMENTS |
| | WITHOUT TRAVELING THROUGH THE GARAGE. PROVIDE PLANS |
| | SHOWING THE EGRESS FROM THE SECOND FLOOR TO THE OUTSIDE |
| | OF THE STRUCTURE. SEC. 801.3 FBC-EXISTING BUILDING AND |
| | SEC. R311.1 FBC-RESIDENTIAL. |
| | |
| | 4- SPECIFY THE HEADROOM IN STAIRWAY AS REQUIRED BY SEC. |
| | R311.7.2 FBC-RESIDENTIAL. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: |
| | A) ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED |
| | AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| | THE OWNER PRIOR TO RECEIVE THE PERMIT. AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION |
| | (2017). |
| | |
| | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE RATIO |
| | IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. OR, |
| | PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE |
| | COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH THE |
| | 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC. |
| | R806.2. |
| | |
| | D) REVISE ITEM #4 ON PAGE 1 OF 4 TO MATCH PLANS. |
| | ACCORDING TO PLANS SUBMITTED. THIS STUDIO IS USED AS |
| | ONE BEDROOM. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY OF |
| | VALUATION SIGNED CONTRACTS INCLUDING DESIGN |
| | PROFESSIONAL FEES. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |