| Plan Review Notes For Permit 19090792 |
| Permit Number |
19090792 |
|
| Review Stop |
NFIP |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2020-03-02 15:05:43 | NFIP REVIEW - PASSED WITH PROVISO'S: | | | | | | UPON SUBMITTAL OF THE UNDER CONSTRUCTION ELEVATION | | | CERTIFICATE - | | | | | | 1. PROVIDE THE ELEVATION OF THE GARAGE FINISHED FLOOR - | | | SEE SECTION C2 (D). | | | | | | 2. CHANGE TYPE OF FLOOD OPENINGS IN GARAGE FROM | | | NON-ENGINEERED TO ENGINEERED PER CONVERSATION WITH | | | CONTRACTOR - SEE SECTION A9 (D). | | | | | | 3. PROVIDE ICC ES EVALUATION REPORT FOR ENGINEERED | | | FLOOD OPENINGS. | | | | | | 4. REDLINE GARAGE FLOOR PLAN WITH FINISHED FLOOR | | | ELEVATION. | | | | | | NOTE: THE GREEHECK AF J60 1X VENTS SHOWN ON PLAN PAGE | | | A-1-1 ARE NOT APPROVED FLOOD VENTS. | | | |
|