| 2019-12-19 11:15:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. ADD NOTE: IRRIGATION REQUIRES SEPARATE PERMIT. ANY |
| | BACKFLOW THAT IS REQUIRED BY THE FBC OR CITY ORD WILL |
| | REQUIRE A SEPARATE PERMIT INSTALLED BY PLUMBING |
| | CONTRACTOR ONLY. |
| | 2. RE: PLAN SHEET P-1; DETAIL 5. PER WPB FBC 107.2.1, |
| | PROVIDE MANUFACTURER?S SPECIFICATION AND INSTALLATION |
| | GUIDE. TO BE CLEAR, ALL PLUMBING CONNECTIONS, BACKFLOW |
| | PREVENTION REQUIREMENTS, TEMPERATURE OUTPUT, WORKING |
| | PRESSURE, PRESSURE RATINGS, SAFETY DEVICES, WASTE |
| | DISCHARGE TEMPERATURE, ELECTRICAL CHARACTERISTICS, ETC. |
| | SHALL BE INCLUDED |
| | INDICATE TEMPERATURE OF DISCHARGE; IF IN EXCESS OF 140 |
| | DEGREES F THEN PER FBC RES P2601.1 AND FBC PL 702.5, |
| | SANITARY PIPING MATERIAL RECEIVING THE DISCHARGE SHALL |
| | BE RATED FOR THE TEMPERATURE OF THE DISCHARGE WASTE AND |
| | SHALL CONFORM TO THE TABLES OF FBC PL 702.1, 702.2, |
| | 702.3 AND 702.4 OR PROVIDE AFTERCOOLER WITH APPROPRIATE |
| | BACKFLOW PREVENTION. |
| | 3. SEE PLAN SHEET P-1: TO CONFORM WITH THE DEFINITION |
| | OF A BUILDING DRAIN AS STATED IN FBC RES R202, PLEASE |
| | NOTE THAT THERE ARE FOUR SEPARATE BUILDING DRAINS |
| | SERVING THE FOLLOWING AREAS; CABANA, NORTH SIDE OF MAIN |
| | HOUSE, SOUTH SIDE OF MAIN HOUSE AND GARAGE. PER FBC RES |
| | P3102.1, PROVIDE A VENT TO THE EXTERIOR FOR EACH THE |
| | NORTH SIDE AND THE SOUTH SIDE OF THE MAIN HOUSE. |
| | 4. SHOWER IN HIS BATH IS NOT VENTED IN ACCORDANCE WITH |
| | FBC RES P3108.1. INDIVIDUALLY VENT TO COMPLY WITH FBC |
| | RES P3105.1. |
| | 5. WATER CLOSET IN HIS BATH IS NOT VENTED. INDIVIDUALLY |
| | VENT TO COMPLY WITH FBC RES P3105.1. |
| | 6. BRANCH DOWNSTREAM OF WASHER SHALL BE SIZED 3? PER |
| | FBC RES P3005.1.6 |
| | 7. SHOWER IN HER BATH SHALL BE LABELED ON SANITARY |
| | ISOMETRIC WPB FBC 107.2.1 |
| | 8. LAVATORY IN ROOF BATH SHALL BE LABELED ON SANITARY |
| | ISOMETRIC WPB FBC 107.2.1 |
| | 9. SHOWER IN HER BATH SHALL CONNECT ABOVE THE WATER |
| | CLOSET PER FBC RES P3107.3 OR BE INDIVIDUALLY VENTED |
| | PER FBC RES P3105.1. PER FBC RES P3105.2, THE SHOWER |
| | FIXTURE DRAIN SHALL NOT RISE VERTICALLY ABOVE THE |
| | CONNECTION OF THE VENT. |
| | 10. LAVATORY IN HER BATH SHALL CONNECT TO THE |
| | HORIZONTAL SECTION OF THE TUB FIXTURE DRAIN PER FBC RES |
| | P3108.1 AND FBC RES P3105.2, OR THE TUB SHALL BE |
| | INDIVIDUALLY VENTED PER FBC RES P3105.1. |
| | 11. SEE PLAN SHEET P-1: PER FBC RES 2601.1 AND FBC PL |
| | 607.2, PROVIDE RECIRCULATED HOT WATER PIPING FOR ANY |
| | HOT WATER DISTRIBUTION SYSTEM THAT EXCEEDS 50? FROM HOT |
| | WATER SOURCE TO FARTHEST OUTLET.PER WPB FBC 107.2.1, |
| | PROVIDE NOTE STATING THE SAME. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19090792 3030 WASHINGTON RD |
| | |
| | |