Plan Review Notes
Plan Review Notes For Permit 19090792
Permit Number 19090792
Review Stop G
Sequence Number 2
Notes
Date Text
2019-12-19 13:04:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 GAS COMMENTS: DENIED
  
 1. PLAN SHEET P-4: GAS RISER DIAGRAM IS MISSING SECOND
 FLOOR FIREPLACE. PER WPB FBC 107.2.1 AND 107.3.5.3
 (12), INCLUDE IN DIAGRAM.
 2. PLAN SHEET P-4 REGARDING "GAS NOTES & CALCULATIONS",
 DELETE NOTE "PROVIDE A 1-1/4" GAS LINE PER:".
 3. PLAN SHEET A-1.1 AND A-2.2 DO NOT NOTE TWO OF THE
 FIVE FIREPLACES NOTED ON PLAN SHEETS P-1 AND P-2 AND ON
 P-4 TOTAL GAS LOAD GAS EQUIPMENT SCHEDULE. PER WPB FBC
 107.2.1, PLEASE CLARIFY.
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) FOR FIREPLACES PER FBC FG
 SECTIONS 502 THRU 505 OR FBC RES SECTIONS G2426 THROUGH
 G2439.
 5. PER WPB FBC 107.2.1, PROVIDE A NOTE STATING "PLASTIC
 PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY.
 PLASTIC PIPE SHALL NOT BE USED WITHIN OR UNDER ANY
 BUILDING OR SLAB." TO COMPLY WITH FBC FG 404.17.1 AND
 FBC RES G2415.17.1.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19090792 3030 WASHINGTON RD


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved