Plan Review Notes
Plan Review Notes For Permit 19090792
Permit Number 19090792
Review Stop E
Sequence Number 2
Notes
Date Text
2019-12-16 09:21:56PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SERVICE OUTLET AT CU-1 & CU-6.
 E3901.12 HVAC OUTLET.
  
 2. AVAILABLE FAULT CURRENT FROM FPL TRANSFORMER IS
 30684. FAULT CURRENT USED ON PAGE E-5 FOR AVAILABLE
 FAULT CURRENT CALCULATIONS IS 52,205. PLEASE CORRECT.
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10 & FBC RE E3404.3
  
 3. REMOVE PANEL DP FROM RISER DIAGRAHM. PANEL DP IS TO
 BE REMOVED FROM SOW PER RESPONSE LETTER FROM DESIGNER.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PANEL B SHOWS A TOTAL LOAD OF 119 AMPS. OVERCURRENT
 PROTECTION FROM MDP IS 100 AMPS. PLEASE CORRECT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  