| 2019-10-21 10:51:18 | PLUMBING 1ST REVIEW**DENIED** PLEASE ADD NOTE |
| | IRRIGATION REQUIRES SEPARATE PERMIT. ANY BACKFLOW THAT |
| | IS REQUIRED BY THE FBC OR CITY ORD WILL REQUIRE A |
| | SEPARATE PERMIT INSTALLED BY PLUMBING CONTRACTOR ONLY. |
| | |
| | 1) PROVIDE SHOWER PAN DETAIL SHOWING MATERIAL TO BE |
| | USED AND 2% SLOPE. FBCR-P 2709. |
| | |
| | 2) PROVIDE STEAM UNIT DRAIN DETAIL FOR HIS STEAM UNIT. |
| | FBC 107.2.1 |
| | |
| | 3) THE CABANA BEING THAT IT HAS ITS OWN BUILDING DRAIN |
| | WITH NOT PERMIT THE USE OF AN AAV AS IT WILL REQUIRE A |
| | VENT TO THE OUTDOORS. FBCR-P3102.1 |
| | |
| | 4) PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING. |
| | SEE MARK UPS ON ISO SHEET SHOWING ERRORS. THE FOLLOWING |
| | COMMENTS APPLY |
| | |
| | A-ONLY 1 WET VENTED FIXTURE IS PERMITTED BEYOND THE |
| | VENT. FBCR-P 3102.1 |
| | B-CAN NOT USE THE VENT STACK ON A LOWER LEVEL WET VENT |
| | FOR 2ND FLOOR BATHROOM. FBCR-P 3108.1 |
| | C- SHOWER MUST BE VENTED AND DIRECTLY CONNECTED INTO |
| | THE BATHROOM GROUP WET VENT. FBCR-P3108.1 |
| | D- PROVIDE SIZING OF EACH SECTION OF BUILDING DRAIN IN |
| | THE HIGHLIGHTED SECTIONS. FBC 107.3.5 |
| | E-NO OTHER FIXTURE OTHER THEN THOSE FIND IN THE |
| | BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE |
| | BATHROOM GROUP WET VENT. |
| | |
| | 5) PROVIDE NOTE THAT ACCESS TO ALL AAV SHALL BE |
| | PROVIDED. FBCR-P3114.5 |
| | |
| | 6) PROVIDE BRANCH LINE SIZE OF WASHING MACHINE. PLEASE |
| | NOTE MUST BE 3? IN ORDER TO USE AAV PER THE |
| | INSTALLATION MANUAL FOR ALL AAV?S. FBCR-P 3114.2 |
| | |
| | 7) PROVIDE STORM ISOMETRIC DRAWING. FBC 107.3.5 |
| | |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH (CGASOLUTIONS) |
| | [email protected]? |
| | 561-248-2703 |
| | |
| | |
| | |