2019-10-21 10:51:48GAS 1ST REVIEW**DENIED** A SEPARATE GAS PERMIT FOR THE
 HOME AND SEPARATE GENERATOR PERMIT IS REQUIRED. FBC
 105.1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER. 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2. SECTION OF PIPING WHICH I
 BUBBLED IN ON THE ISOMETRIC ARE MISSING CUT SECTIONS.
 PLEASE ADD TO CLARIFY.
  
 2. YOUR CALCULATIONS FOR COMBUSTION AIR LIST AN AIR KIT
 IS REQUIRED FOR THE LIBRARY IS REQUIRED. PLEASE PROVIDE
 HOW YOU INTENT TO COMPLY WITH THE REQUIRED MAKE UP AIR.
 FBCR G2407.9.3
  
 3. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC-RES. SEC. G2421.1.
  
 4. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. IT APPEARS THE
 TANKLESS OUTSIDE OF BATHROOM #1 MAY BE TOO CLOSE.
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6. R405/2017 FORM ONLY LIST 1 TANKLESS GAS WATER HEATER
 THIS HOME HAS 3. PLEASE CORRECT AND SUBMIT MANUFACTURES
 INSTALLATION MANUAL TO SHOW THEY COMPLY WITH THE 2017
 FLORIDA ENERGY CODE AND FEDERAL MIN STANDARDS. FBC
 107.3.5
  
 7. PLEASE ADD NOTE THAT ALL EXTERIOR PIPING SHALL HAVE
 A PROTECTIVE PAINT COATING. NFPA 54
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703
  
  