| 2019-10-12 12:26:46 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FIRST FLOOR |
| | |
| | 1. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS.(FOYER AND FAMILY ROOM) FIXED |
| | PANELS IN FAMILY ROOM COUNT FOR WALL SPACING. |
| | |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. |
| | PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1 |
| | |
| | 2.PROVIDE NOTE ON PLAN STATING LOW VOLTAGE, GENERATOR, |
| | AND ELEVATOR WILL REQUIRE SEPARATE PERMITS. FBC 107.2.1 |
| | FBC 105.1 |
| | |
| | 3. RECEPTACLE REQUIRED FOR PATIO OUTSIDE OF BEDROOM #1 |
| | NEC 210.52E3 |
| | |
| | 4. DISCONNECTS BEHIND CU2 DO NOT HAVE THE REQUIRED |
| | WORKING CLEARANCE. NEC 110.26A |
| | |
| | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | |
| | 6. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8(A)(9); FBC RE E3902.9 |
| | |
| | SECOND FLOOR, |
| | |
| | 1. RECEPTACLES REQUIRED ON ALL BALCONIES OUTSIDE. NEC |
| | 210.52E3 |
| | |
| | 2.PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AND SWITCH |
| | CONTROLLED LIGHT FOR SERVICING EACH AHU LOCATED IN AN |
| | ATTIC. FBC MECHANICAL CODE M306.3.1 |
| | |
| | 3. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8(A)(9); FBC RE E3901.2.9 |
| | |
| | SERVICE/RISER |
| | |
| | 1. FAULT CURRENT CALCULATION FOR SERVICE IS BLURRY AND |
| | NOT READABLE, ALSO PROVIDE FAULT CURRENT LETTER FROM |
| | POWER UTILITY (FPL). FBC 107.2.1 |
| | |
| | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | 3. LOCATION OF DOCK PANEL NOT SHOWN? HOW FAR AWAY FROM |
| | SERVICE IS DOCK PANEL LOCATED AND WHAT IS THE VOLTAGE |
| | DROP? FBC 107.2.1 |
| | |
| | 4. PANEL SCHEDULE FOR DOCK NOT SHOWN, WHAT IS LOAD OF |
| | DOCK PANEL? FBC 107.2.1 |
| | |
| | 5.THE RISER DIAGRAM SHOWS THE FEEDERS FOR ALL PANELS |
| | FED FROM MDP, EXCEPT PANEL B, AS "TWO SETS OF 350 MCM |
| | CU". SHOW ACTUAL FEEDER SIZE FOR ALL PANELS. FBC |
| | 107.2.1 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |