Plan Review Notes
Plan Review Notes For Permit 19090792
Permit Number 19090792
Review Stop E
Sequence Number 1
Notes
Date Text
2019-10-12 12:26:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FIRST FLOOR
  
 1. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS.(FOYER AND FAMILY ROOM) FIXED
 PANELS IN FAMILY ROOM COUNT FOR WALL SPACING.
  
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1
  
 2.PROVIDE NOTE ON PLAN STATING LOW VOLTAGE, GENERATOR,
 AND ELEVATOR WILL REQUIRE SEPARATE PERMITS. FBC 107.2.1
 FBC 105.1
  
 3. RECEPTACLE REQUIRED FOR PATIO OUTSIDE OF BEDROOM #1
 NEC 210.52E3
  
 4. DISCONNECTS BEHIND CU2 DO NOT HAVE THE REQUIRED
 WORKING CLEARANCE. NEC 110.26A
  
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 6. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
  
 SECOND FLOOR,
  
 1. RECEPTACLES REQUIRED ON ALL BALCONIES OUTSIDE. NEC
 210.52E3
  
 2.PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AND SWITCH
 CONTROLLED LIGHT FOR SERVICING EACH AHU LOCATED IN AN
 ATTIC. FBC MECHANICAL CODE M306.3.1
  
 3. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3901.2.9
  
 SERVICE/RISER
  
 1. FAULT CURRENT CALCULATION FOR SERVICE IS BLURRY AND
 NOT READABLE, ALSO PROVIDE FAULT CURRENT LETTER FROM
 POWER UTILITY (FPL). FBC 107.2.1
  
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 3. LOCATION OF DOCK PANEL NOT SHOWN? HOW FAR AWAY FROM
 SERVICE IS DOCK PANEL LOCATED AND WHAT IS THE VOLTAGE
 DROP? FBC 107.2.1
  
 4. PANEL SCHEDULE FOR DOCK NOT SHOWN, WHAT IS LOAD OF
 DOCK PANEL? FBC 107.2.1
  
 5.THE RISER DIAGRAM SHOWS THE FEEDERS FOR ALL PANELS
 FED FROM MDP, EXCEPT PANEL B, AS "TWO SETS OF 350 MCM
 CU". SHOW ACTUAL FEEDER SIZE FOR ALL PANELS. FBC
 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved