| Plan Review Notes For Permit 19090626 |
| Permit Number |
19090626 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-18 15:40:44 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1-- FLAT ROOF NOA 1--0622.21 SUBMITTED: SELECTED | | | ASSEMBLY ON PAGE 12 OF 19 DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED | | | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER | | | AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 | | | ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE | | | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|