| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19090625 |
| | 9/25/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE $12,000 PROJECT COST FOR THE WALKIN COOLERS AND |
| | FREEZERS IS AN EXTREMELY LOW VALUE FOR THE SCOPE OF |
| | WORK. THIS APPEARS TO BE THE COST OF LABOR ONLY AND |
| | DOES NOT INCLUDE THE WALKIN BOXES, REFRIGERATIONS |
| | SYSTEMS, LIGHTS, PIPINGS ETC. PLEASE REFER TO SECTION |
| | 109.3 WPB: PERMIT FEES ARE BASED ON LABOR, MATERIALS, |
| | EQUIPMENT AND APPLIANCES, DESIGN FEES, PROFIT AND |
| | OVERHEAD. PLEASE PROVIDE COPIES OF CONTRACTS, INVOICES, |
| | AND ESTIMATES FOR THE ENTIRE PROJECT TO VERIFY ACCURATE |
| | VALUE. |
| | |
| | 2) THE PLANS DO NOT SHOW THE LOCATIONS OF THE REMOTE |
| | CONDENSERS AND DO NOT PROVIDE ENGINEERED INSTALLATION |
| | DETAILS- SECTION 107.3.5.1.1 WPB AND 301.15 FBC M. |
| | |
| | 3) THE SUBMITTED FOOD SEVICE AND WALKIN PLANS ARE SHOP |
| | DRAWINGS WHICH REQUIRE APPROVAL STAMPS BY THE ENGINEER |
| | OF RECORD- SECTION 107.2.1 & 107.2.1.2 WPB |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |