| Plan Review Notes For Permit 19090610 |
| Permit Number |
19090610 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-18 18:52:54 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL10497-R6 | | | SUBMITTED: | | | SELECTED ASSEMBLY W-41 DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES. THE DESIGN PRESSURES OF | | | BONDED ROOF ASSEMBLIES NEED TO MEET OR EXCEED THE | | | DESIGN PRESSURES FOR ALL ROOF ZONES. ASSEMBLY W-41 | | | DOESN'T MEET HE DESIGN PRESSURES FOR ALL ROOF ZONES. | | | THEREFORE, ANOTHER ASSEMBLY NEEDS TO BE SELECTED. SEE | | | LIMITATION #5.8 ON PAGE 4 OF 5 OF PRODUCT APPROVAL | | | SUBMITTED. NOTE: ACCORDING TO SEC. R301.2.1.4 | | | FBC-RESIDENTIAL, THIS BUILDING IS LOCATED IN EXPOSURE | | | "D". TAKE THIS INTO CONSIDERATION WHEN SELECTING | | | ANOTHER BONDED ASSEMBLY. THE DESIGN PRESSURES FOR | | | BUILDINGS LOCATED IN EXPOSURE "D" ARE HIGHER. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|