Plan Review Notes
Plan Review Notes For Permit 19090606
Permit Number 19090606
Review Stop B
Sequence Number 3
Notes
Date Text
2020-01-14 16:14:472017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090606
 ADD: 1645 PALM BEACH LAKES BLVD. SUITE: 800
 CONT: NIXON HOME IMPROVEMENTS
 TEL: 561-305-8215
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN. 14/2020
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) NEW COMMENT. THE COVERSHEET & SHEET A-2 BOTH SHOW AN
 OCCUPANT LOAD OF 97 FOR 685 SQ. FT. OF THE BREAK ROOM.
 THE AREA OF THE BREAK ROOM IS CLOSER TO 24.5 X 27.5 =
 674 SQ. FT./ 15 SQ. FT. PER OCC= 45 OCCUPANTS PLEASE
 CORRECT. SEE 2017 FBC-B TABLE 1004.1.2. ASSEMBLY WITH
 TABLES AND CHAIRS. 15 SQ. FT. OCCUPANT LOAD FACTOR.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  