| Plan Review Notes For Permit 19090606 |
| Permit Number |
19090606 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-11 14:20:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET CRV - THERE ARE INDICATION OF THE BUILDING HAS | | | "NO SPRINKLERED". | | | | | | THIS IS AN EXISTING HIGH RISE WITH A FULL FIRE | | | SPRINKLER SYSTEM. FIRE SPRINKLER PROTECTION IS REQUIRED | | | WITHIN THIS PROPOSED | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 2) ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE ON SHEET A-2. | | | | | | | | | | | | 3) SHEET A 2 - THE CREATED BREAKROOM IS AN ASSEMBLY | | | OCCUPANCY; HOWEVER, NO OCCUPANCY LOAD NO SEATING PLAN | | | IS INDICATED. | | | | | | PLEASE REVIEW AND PROVIDE A PROPOSED SEATING PLAN AND | | | OCCUPANCY LOAD. | | | | | | | | | | | | 4) SHEET A 1 - DOOR 1 IS INDICATED WITHIN THE DOOR | | | SCHEDULE HOWEVER, THE HARDWARE AND LOCKING LATCHING IS | | | NOT PROVIDED. | | | | | | THESE DOOR PROVIDE EGRESS TO THE NEW ASSEMBLY AREA AND | | | THE HARDWARE SHALL COMPLY WITH NFPA 101, CH 7, MEANS OF | | | EGRESS AND CH 12, NEW ASSEMBLY OCCUPANCIES. | | | | | | PLEASE REVIEW AND PROVIDE COMPLIANT HARDWARE. | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|