2019-10-11 14:20:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET CRV - THERE ARE INDICATION OF THE BUILDING HAS
 "NO SPRINKLERED".
  
 THIS IS AN EXISTING HIGH RISE WITH A FULL FIRE
 SPRINKLER SYSTEM. FIRE SPRINKLER PROTECTION IS REQUIRED
 WITHIN THIS PROPOSED
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE ON SHEET A-2.
  
  
  
 3) SHEET A 2 - THE CREATED BREAKROOM IS AN ASSEMBLY
 OCCUPANCY; HOWEVER, NO OCCUPANCY LOAD NO SEATING PLAN
 IS INDICATED.
  
 PLEASE REVIEW AND PROVIDE A PROPOSED SEATING PLAN AND
 OCCUPANCY LOAD.
  
  
  
 4) SHEET A 1 - DOOR 1 IS INDICATED WITHIN THE DOOR
 SCHEDULE HOWEVER, THE HARDWARE AND LOCKING LATCHING IS
 NOT PROVIDED.
  
 THESE DOOR PROVIDE EGRESS TO THE NEW ASSEMBLY AREA AND
 THE HARDWARE SHALL COMPLY WITH NFPA 101, CH 7, MEANS OF
 EGRESS AND CH 12, NEW ASSEMBLY OCCUPANCIES.
  
 PLEASE REVIEW AND PROVIDE COMPLIANT HARDWARE.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  