| Plan Review Notes For Permit 19090570 |
| Permit Number |
19090570 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-10-21 09:06:31 | PROVISO- REVIEWED REMOTELY BY TIM HUNT | | | | | | 1) SHT-A2.1.1*SHOWER HEAD SHALL BE MAX FIX 48? OR ON A | | | SLIDE BAR WITH THE GRIPPING SURFACE @ MAX 48?. FBC-ACC | | | 608.5.1 | | | 2) SHT-P3 ALL NEW HOT AND RETURN WATER PIPING SHALL BE | | | INSULATED WITH 1? WALL MIN. FBC-PLB 607.5, FBC-ENERGY | | | C404.4 | | | 3) SHT-P-3 MIRROR DETAIL ADDED 40? MAX IS TO THE | | | REFLECTIVE SURFACE OF THE MIRROR AND NOT THE BOTTOM | | | EDGE OR TRIM. FBC-ACC 603.3 | | | | | | | | | |
|