| Plan Review Notes For Permit 19090557 |
| Permit Number |
19090557 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-12-12 16:03:49 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | SEE PLAN SHEET 4 | | | A. PROVIDE ACCESSIBLE SHUT OFF VALVES FOR THE TUB PER | | | FBC PL 606.2 AND 606.3 | | | B. REPLACE EXISTING WATER HEATER WITH NEW AND PROVIDE | | | EXPANSION TANK; SEE ATTACHED SUBMITTAL | | | C. PROVIDE VACUUM BREAKER FOR HAND HELD SHOWER; | | | D. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS DEFERRED SUBMITTALS THE FOLLOWING ITEMS INCLUDED | | | WITH THE K-156-LCP BELAY WALK IN TUB: 1)K-368 HAND | | | SHOWER HOLDER; 2)K-438-K BATH VALVE WITH DIVERTER. THE | | | DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON SITE | | | PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK. | | | |
|