| 2019-09-27 18:06:31 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE MANUFACTURE SPECIFICATIONS FOR TUB VALVE AND |
| | NEW WATER HEATER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SEPERATE SHUT OFF VALVES REQUIRED FOR TUB SHALL BE |
| | ACCESSIBLE. PER FBC PL 606.2 606.3 |
| | |
| | 3. THE HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL |
| | BATHTUBS SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF |
| | 120?F (49?C) BY A WATER-TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE |
| | SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION |
| | TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION 424.3. PER |
| | FBC PL THE HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL |
| | BATHTUBS SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF |
| | 120?F (49?C) BY A WATER-TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE |
| | SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION |
| | TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION 424.3. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |