2019-09-27 18:06:311ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPECIFICATIONS FOR TUB VALVE AND
 NEW WATER HEATER. PER WPB AMEND TO FBC 107.2.1
  
 2. SEPERATE SHUT OFF VALVES REQUIRED FOR TUB SHALL BE
 ACCESSIBLE. PER FBC PL 606.2 606.3
  
 3. THE HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL
 BATHTUBS SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF
 120?F (49?C) BY A WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE
 SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION 424.3. PER
 FBC PL THE HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL
 BATHTUBS SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF
 120?F (49?C) BY A WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE
 SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION 424.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  